![ADT Commercial Fire & Burglary Alarm System FOCUS 200 PLUS Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/adt/commercial-fire-and-burglary-alarm-system-focus-200-plus/commercial-fire-and-burglary-alarm-system-focus-200-plus_installation-and-setup-manual_2854006040.webp)
FOCUS 200 PLUS Installation and Setup Guide
5-12
(A) WIRING DIAGRAM FOR TYPICAL SYSTEM-POWERED BA SENSOR
BLK
RED
YEL
BLU
OR GRN
1
2
3
4
5
6
EOL RESISTOR
IN PID (NOTE 3)
(NOTE 1)
HEADER
RECEPTACLE
PID BRANCH
CABLE CONNECTOR
1
2
3
4
(NOTE 2)
D6441-4 CABLE OR 36468
BRANCH CABLE (NOTE 7)
LOW SIDE
HIGH SIDE
+12VDC
- 12VDC
G
AL
TA
RESISTOR
3010 OHM, 1%, 1/2 W
(SCN 975305) (NOTE 4)
(NOTE 5)
+
(NOTE 6)
BLK
RED
YEL
BLU
OR GRN
HEADER
RECEPTACLE
PID BRANCH
CABLE CONNECTOR
1
2
3
4
D6441-4 CABLE OR 36468
BRANCH CABLE (NOTE 7)
LOW SIDE RETURN
HIGH SIDE RETURN
1
2
3
4
5
6
EOL RESISTOR
ON PID BOARD
(NOTE 1)
G
(NOTE 5)
AL
TA
+
(NOTE 6)
HIGH SIDE FEED
LOW SIDE FEED
TO SEPARATE
POWER SOURCE
BA SENSOR
TERMINALS
(B) WIRING DIAGRAM FOR TYPICAL INDEPENDENTLY POWERED BA SENSOR
NOTES:
1. LETTER "G" ON PRINTED WIRING BOARD INDICATES PIN 1 OF HEADER.
2. RECEPTACLE POSITION ON HEADER INDICATES A SYSTEM-POWERED SENSOR.
3. EOL RESISTOR IN PID IS NOT USED FOR SYSTEM-POWERED SENSOR.
4. EOL RESISTOR IS ORDERED SEPARATELY FOR SYSTEM-POWERED SENSOR.
5. ADD JUMPER BETWEEN TA AND AL RELAY CONTACTS AS SHOWN.
6. TAMPER CONTACT IS WIRED ELECTRICALLY AHEAD OF ALARM CONTACT.
7. 6468 BRANCH CABLE CAN BE USED IN PLENUMS.
{
Figure 5-4: Connections of BA Sensors with Field Wiring Terminals to PID
( )
(+)
1
2
3
4
5
6
HEADER
RECEPTACLE
PID CABLE
CONNECTOR
1
2
3
4
(NOTE 1)
NOTES:
1. MAXIMUM CURRENT TO SOUNDER = 85mA.
2. PROGRAM PID AS COPID POINT, SELECTING
DESIRED FUNCTION THAT WILL CAUSE SOUNDER
TO TURN ON (e.g. BA FIXED, FA, SUPERVISORY).
( )
(+)
PA400W
SOUNDER
(INDOOR)
Figure 5-5: Using a PID to Turn On a PA400W Sounder
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...