FOCUS 200 PLUS Installation and Setup Guide
10-20
Identifying the ACIU in the CCC Transmission
The table below shows the information sent to the CCC for the various trouble conditions for each unit
number:
Unit Number
CCC Transmission
0
DA32, DT32, or DR32
1
DA32, DT33, or DR33
2
DA34, DT34, or DR34
3
DASS, DT35, or DRSS
4
DA36, DT36, or DR36
5
DA37, DT37, or DR37
6
DA38, DT38, or DR33
7
DA39, DT39, or DR39
DA = Tamper, DT = Trouble (battery or strike wiring), DR = Restore
Super-Degraded Mode
If the control unit fails or the ACIU loses communication with the control unit, the ACIU goes into the
Super-Degraded mode, operating on its battery power. In this mode, the reader will recognize only the
last 63 different card/key codes that were granted access. This allows these people to continue to gain
access in the interim until normal operation is restored.
Attempts at access during the Super-Degraded mode, whether they are successful or not, will not be
logged in the History Log.
Troubleshooting
The following table describes access control troubleshooting procedures:
Symptom
Probable Cause
Corrective Action
1
Battery is not fully charged
or is not properly connected
to ACIU.
1
Make sure that battery is fully charged and is properly
connected to ACIU.
2
Insufficient power to
reader.
2
Check for 5VDC between TB2-1 (-) and TB2-2 (+). If
you are using a Marlok Keylok or Keyreader, key must
be fully inserted in keyway for this measurement.
A.
If reading is too low, either RS-485 bus voltage to
ACIU is too low or ACIU is defective.
B.
If reading is OK, problem is in reader or wiring to
reader.
3
Insufficient voltage to
ACIU.
3
Check for at least 12.5VDC across TB1-1 (-) and TB1-2
(+).
A.
If reading is too low, add a local power supply.
B.
If reading is zero or if polarity is reversed, check
wiring to TB1.
4
Defective ACIU.
4
Disconnect all wires from TB2. If voltage between TB2-
1 (-) and TB2-2 (+) is not 5VDC, replace ACIU.
5
Wrong reader.
5
Replace reader with one that is rated to operate
between 4.75 and 5.25VDC.
Red LED on reader or
keylok does not go on.
6
Defective reader.
6
Disconnect all reader wires on TB2, except wires TB2-1
(-) and TB2-2 (+). If reader had connection to TB2-6,
momentarily connect this wire to TB2-1. If red LED
does not light, replace reader.
Содержание Commercial Fire & Burglary Alarm System FOCUS 200 PLUS
Страница 2: ......
Страница 22: ...FOCUS 200 PLUS Installation and Setup Guide 3 6...
Страница 28: ...FOCUS 200 PLUS Installation and Setup Guide 4 6...
Страница 64: ...FOCUS 200 PLUS Installation and Setup Guide 6 8...
Страница 76: ...FOCUS 200 PLUS Installation and Setup Guide 7 12...
Страница 110: ...FOCUS 200 PLUS Installation and Setup Guide 10 24...
Страница 166: ...FOCUS 200 PLUS Installation and Setup Guide 16 4...
Страница 196: ...FOCUS 200 PLUS Installation and Setup Guide 21 4...
Страница 204: ...FOCUS 200 PLUS Installation and Setup Guide 22 8...
Страница 210: ...Index Index 6...
Страница 214: ...A 4...
Страница 216: ...9 3l K3471V2 1 00 ADT Security Services Inc One Town Center Road Boca Raton FL 33486 Copyright 1999...