background image

D900-28-00 

I56-1796-011R

For use with the following models:
Strobes - 12/24 volt:  S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW
Combo - 12/24 volt:  P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, P1224MCPW
Horns - H12/24, H12/24W

Suffix “W” indicates white housing models. Suffix “SP” indicates “FUEGO” (Spanish word for “FIRE”) lettering on housing.
Suffix “P” indicates plain housing (no lettering).
The Products to which this manual applies may be covered by one or more of the 
following U.S. Patent numbers: 5,914,665; 5,850,178; 5,598,139; 6,049,446; 6,133,843; 6,522,261; 6,661,337; 5,931,569; 6,793,375; 6,822,400; 6,833,783; 6,838,997

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

General Description

The  SpectrAlert  series  notification  appliances  are  designed  to 
meet the requirements of most agencies governing these devices, 
including: NFPA, ADA, The National Fire Alarm Code, UL, ULC, 
FM, CSFM, MEA. Also, check with your local Authority Having 
Jurisdiction for other codes or standards that may apply.
The SpectrAlert series can be installed in systems using 12- or 24-
volt panels having DC or full-wave rectified (FWR) power supplies. 
The series can also be installed in systems requiring synchroniza-
tion (module MDL or compatible equivalent required) or systems 
that do not require synchronization (no module required).

NOTICE:

 This manual shall be left with the owner/user of this equipment.

Fire Alarm System Considerations

Temporal and Non-Temporal Coded Signals:

The American National Standards Institute and the National Fire 
Alarm Code require that all horns used for building evacuation in-

Specifications

Automatic selection for 12 or 24 volt rated operation (DC or Full-Wave Rectified)

Electrical

Horns, Strobes, and 
 

Horn/Strobes Voltages: 

Regulated 12 DC/FWR and Regulated 24 DC/FWR

Operational Voltage Ranges: 

12V=8-17.5 Volts; 24V=16-33 Volts

Synchronous Applications
 

with MDL Module: 

12V=9-17.5 Volts; 24V=17-33 Volts

Operational Humidity Range: 

10-93% RH (non-condensing)

NOTE: Horn units will operate on walk tests with on-time durations of .25 sec. or greater.

Flash Rate: 

1 flash per second 

Operating Temperature: 

32° F to 120° F (0° C to 49° C)

Selectable Light Outputs: 

All candelas are selectable via a manual slide switch.

12/24 Volt Applications: 

15 or 15/75 candela

24 Volt Application: 

30, 75, 110 candela

 

 15/75  is  listed  at  15  candela  per  UL  1971  but  will  provide  75  candela  on  axis 
(straight ahead). 15, 30, 75, or 110 are rated for that candela.

Sound Output: 

 Sound output levels are established at Underwriters Laboratories in their reverber-
ant room. Always use the sound output specified as UL Reverberant Room when 
comparing products.

Listings: 

UL S5512 (Strobe); UL S4011 (Combo)

Note for Strobes: 

 Do not exceed: 1) 8-17.5 or 16-33 voltage range limit; 2) maximum number of 70 
strobe lights when connecting the MDL Sync module with a maximum line im-
pedance of 4 ohms per loop and; 3) maximum line impedance as required by the 
fire alarm control manufacturer.

The models S1224MC, S1224MCW, S1224MCSP, S1224MCSPW, S1224MCP, S1224MCPW, P1224MC, P1224MCW, P1224MCSP, P1224MCSPW, P1224MCP, and 

P1224MCPW incorporate a patented voltage booster design that has a more consistent flash bulb voltage over the range of candela selections. The benefit to 

the customer is a high quality strobe device.

stalled after July 1, 1996, must produce Temporal Coded Signals.
Signals other than those used for evacuation purposes do not have 
to produce the Temporal Coded Signal. Temporal coding is accom-
plished by interrupting a steady sound in the following manner:

1

/

2

 Sec. 

On

1

/

2

 Sec. 

Off

1

/

2

 Sec. 

On

1

/

2

 Sec. 

Off

1

/

2

 Sec. 

On

1

1

/

2

 Sec. 

Off

Repeats

Power Supply Considerations

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-wave 
rectified) voltage. The system design engineer must calculate the 
number of units used in a zone based on the type of panel supply. 
Be certain the sum of all the device currents do not exceed the 
current capability of the panel. Calculations are based on using 
the  device  current  found  in  the  subsequent  charts  and  must  be 
the current specified for the type of panel power supply used.

SpectrAlert Selectable Output Strobes, 
Horns, and Horn/Strobes

Содержание SpectrAlert S1224MCW

Страница 1: ...nal Humidity Range 10 93 RH non condensing NOTE Horn units will operate on walk tests with on time durations of 25 sec or greater Flash Rate 1 flash per second Operating Temperature 32 F to 120 F 0 C to 49 C Selectable Light Outputs All candelas are selectable via a manual slide switch 12 24 Volt Applications 15 or 15 75 candela 24 Volt Application 30 75 110 candela 15 75 is listed at 15 candela p...

Страница 2: ... 15 75 135 74 127 69 30 93 90 75 158 160 110 208 209 Figure 1B Horn Sound Measurements dBA Selectable Horn Tones 8 17 5V 16 33V Temporal Low Volume Electromechanical 67 75 3000 Hz Interrupted 68 75 High Volume Electromechanical 71 80 3000 Hz Interrupted 72 81 Non Temporal Low Volume Electromechanical 71 79 3000 Hz Interrupted 72 79 High Volume Electromechanical 76 84 3000 Hz Interrupted 77 86 Figu...

Страница 3: ...ch located on the rear of the product while watching the viewing win dow on the side of the reflector Viewing Window A0133 00 Permissible Candela Settings Candela Setting Operating Voltage 12V 24V 15 OK OK 15 75 OK OK 30 OK 75 OK 110 OK Check terminal polarity before wiring For proper operation make sure the correct wire polarity is applied to the unit WARNING Figure 3 Horn Factory Default Setting...

Страница 4: ...include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of dam age unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expr...

Отзывы: