Chapter 6 Deployment of the CPU 821xDP
CPU ADAM 821x
6-28
ADAM 8000 Manual CPU 821x – Rev 1.1
To be compatible to the STEP
®
7 projecting tool from Siemens, you have to
execute the following steps for the System 82xx:
•
Start the hardware configurator from Siemens.
•
Configure a CPU 315-2DP with DP master system (address 2).
•
Add a Profibus slave
ADAM 821x
at address 1.
•
Include the CPU
8214-2BM01
at the plug-in location 0 of the slave
system.
•
Include the output module 8222-1BF00 at plug-in location 1.
For linking-up the CPU 8214DP you have to execute the following steps
after including the GSD-file:
•
Add the Profibus slave
"CPU82xxDP"
(address 3). The DP slave is in
the hardware catalog under:
Profibus-DP > Additional field devices > I/O > ADAM >
ADAM_CPU82xxDP
.
•
Assign memory areas of the CPU to the in- and output of the Profibus-
DP master section in form of Byte blocks. For this, you have to include
the "2Byte output" element on plug-in location 0 and select the output
address 20. Include the "2Byte input" element on plug-in location 1 and
select the input address 10.
•
Save your project.
Including directly connected modules
Including CPU 821xDP
Configuration of
CPU 821xDPM
(Master)