CPU ADAM 821x
Chapter 5 Deployment of the CPU 821xDPM
ADAM 8000 Manual CPU 821x – Rev 1.1
5-5
Project engineering CPU with integrated Profibus-DP master
For the project engineering of the Profibus-DP master you have to use the
hardware manager from Siemens. Your Profibus projects are transferred
via MPI into the CPU 821xDPM by means of the
PLC
functions. The CPU
passes the data on to the Profibus-DP master.
The address allocation and the parameterization of the directly plugged-in
modules takes place via the STEP
7 manager from Siemens in form of a
virtual Profibus system.
For the Profibus interface is standardized in software, you'll have the
complete functionality of our modules at your disposal by including the
GSD-file into the STEP
7 manager.
To be compatible with the STEP
7 projecting tool from Siemens, you have
to execute the following steps for the System 82xx:
•
Project the CPU 315-2DP with the DP master system (address 2).
•
Add the Profibus slave with address 1.
•
Insert the CPU type 8
21xDPM
at plug-in location 0 of the slave system.
•
Include directly plugged-in peripheral modules also via this slave at the
plug-in locations 1...32.
CPU 821xDPM central
DP slaves decentral ...
PB-
Add.:1
PB-
Adr.:3 ... 125
Slot Module
0 821x-2BM01
1
. central
. periphery
.
32
PB-
Add.:2
DP200V
DP200V
ADAM 821x
ADAM821xDP
Note!
For the project engineering of the CPU and the Profibus-DP masters a
thorough knowledge of the STEP
7 manager and the hardware configura-
tor from Siemens is required!
Outline
Compatibility to
STEP
7 manager
from Siemens
Steps of
engineering