PTS PRESSURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
E
-
3
Select an engineering unit best suited for the
application.
Input lower range value using the arrow keys, then
press
. Input the upper range value.
Refer to the
Platinum Standard Series Smart Pres-
sure Transmitter PTS
instruction for mode descrip-
tion.
Make a selection using the arrow keys.
This is a 6-character alphanumeric designation to
represent values in user familiar units.
To select a character, press the key that has the
desired character. Continue to press the key until the
desired character appears. Use the right arrow key to
move to the next character. Use the left arrow key to
go back to the previous character. Press
when finished.
Specify values using the number keypad. The
UNITS
displayed will be those designated in the previous
screen. After entering value press
.
Lower and upper temperature alarms are user con-
figured. The temperature is based on the cell. The
default alarms setting are shown here. The defaults
are also the lower and upper limits of the alarm.
NOTE:
Use
to return to a previous configura-
tion screen from any screen in the configuration pro-
cess.
Key
Display
Comments
E N T E R
ENGINEERING UNIT
→
iH20cmH2OmmHg
PSIMPAKPA
BARSmBARKgcm2
E N T E R
LOWER RANGE VAL.
nn.nn UNITS
UPPER RANGE VAL.
nn.nn UNITS
ENTER
E N T E R
INITIALIZE MODE:
→
LOW
HIGH
E N T E R
FAIL MODE:
→
LOW
HIGH
LAST
E N T E R
ENTER
SECONDARY UNITS
_nnnnnn
ENTER
E N T E R
SECONDARY L. R.
nn.nn UNITS
SECONDARY U. R.
nn.nn UNITS
ENTER
E N T E R
LOWER TEMP ALARM
-40.00
°
C
UPPER TEMP ALARM
85.00
°
C
BACK