PTH PRESSURE TRANSMITTER
CALIBRATION
D
-
7
Select
UPDOWN ARROW KEYS
.
NOTE:
Refer to
for
details about meter value entry.
Adjust transmitter output using the up and down
arrow keys. If configured digitally this adjust display
does not appear.
NOTE:
When increasing or decreasing the mA sig-
nal, the increments of change increase with succes-
sive depressions until the maximum level of change
is reached. By changing direction the smallest incre-
ment of change returns. This technique speeds up
the adjustment process without affecting fine
adjustment.
Adjust the transmitter output using the up and down
arrow keys.
Key
Display
Comments
E N T E R
D/A CAL USING
→
UPDOWN ARROW KEYS
METER VALUE ENTRY
E N T E R
ADJUST TO 4 mA
THEN HIT ENTER
E N T E R
ADJUST TO 20 mA
THEN HIT ENTER
E N T E R
ID TAGNAME
READY