ADDENDUM
10
ZERO TRIM
Use this option if only the LOW (min.) pressure setting is to be calibrated
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select YES.
Select SENSOR TRIM, or select calibration option
with down-arrow key and refer to the appropriate
section. Press
when done.
Select ZERO TRIM.
Apply the pressure equal to the zero value of the
instrument and press
.
The instrument reads the pressure applied and dis-
plays its value. Press
.
C A LI-
B R AT E
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
→
SENSOR TRIM
D-TO-A ADJUST
PV BIAS
SET OUTPUT %
ENTER
E N T E R
FULL TRIM
→
ZERO TRIM
FACTORY TRIM
STATIC TRIM
E N T E R
APPLY 0 INPUT
TO SENSOR
THEN HIT ENTER
ENTER
E N T E R
APPLIED ZERO INPUT:
value units
PRESS ENTER
TO CONTINUE
ENTER
E N T E R
ID TAGNAME
READY