INTRODUCTION
H
-
1
APPENDIX H - EQN TEMPERATURE TRANSMITTER
INTRODUCTION
This appendix covers the configuration and calibration functions of
the EQN Temperature Transmitter.
Refer to
in Section 4 for information on
the following functions:
NOTE:
To change calibration or configuration parameters of a smart
field device that is connected to an IMFBS01 module, the device
must be taken off-line. This is done at the INFI 90 OPEN console.
CREATE/MODIFY CONFIGURATION
A configuration can be created off-line, without a connected field
device. Refer to Figure
for an overview of the configuration
function. The following table details the configuration process.
•
Send configurations.
•
Select configurations.
•
Get configurations.
•
Erase configurations.
•
View configurations.
•
Operational functions.
Figure H-1. Configuration Flowchart (EQN)
T01618A
SELECT
DEVICE
TYPE
SELECT
MODE
SELECT
SENSOR
TYPE
SELECT
OHMS
SELECT
mV
SELECT
RTD
TYPE
SELECT
NUMBER OF
ELEMENTS
SELECT
ENGINEERING
UNITS
SELECT
NUMBER OF
ELEMENTS
SELECT
THERMOCOUPLE
TYPE
SELECT
APPROXIMATION
METHOD
ENTER
CONFIGURATION
ID TAG
ENTER 5
INPUT/OUTPUT
POINTS
ENTER LOWER/UPPER
SECONDARY
RANGE VALUES
SELECT
OUTPUT
TYPE
ENTER
LOWER/UPPER
RANGE VALUES
SELECT
OUTPUT
ACTION
SELECT
FAIL
MODE
SELECT
INITIALIZE
MODE
STORE
CONFIGURATION
ENTER
DAMPING
VALUE
ENTER
SECONDARY
UNITS
SELECT
TRANSMITTER
TYPE
ENTER
CHANNEL
NUMBER
DIGITAL
LINEAR
FUNCTION
GENERATOR
ABB FSK
ANALOG
T/C
RTD
OHMS
mV
C
O
N
F
I
G
U
R
E
Содержание STT04
Страница 1: ...INSTRUCTION MANUAL Smart Transmitter Terminal STT04 PN25054 ...
Страница 179: ...TBN580 TRANSMITTER CALIBRATION K 12 Key Display Comments ENTER ID TAGNAME READY ...
Страница 253: ...AS800 PRESSURE TRANSMITTER CALIBRATION P 11 TEMPERATURE CALIBRATION is complete ENTER ID TAGNAME READY ...