APPENDIX C - EQS TEMPERATURE TRANSMITTER
INTRODUCTION
This appendix covers the configuration and calibration functions of
the EQS Temperature Transmitter. Refer to
in Section 4 for information on the following functions:
NOTE:
To change calibration or configuration parameters of a smart
field device that is connected to an IMFBS01 module, the device
must be taken off-line. This is done at the INFI 90 OPEN console.
CREATE/MODIFY CONFIGURATION
Configuration can be created off-line, without a connected field
device. Refer to Figure
for an overview of the configuration
function. The following table details the configuration process.
•
Send configurations.
•
Select configurations.
•
Get configurations.
•
Erase configurations.
•
View configurations.
•
Operational functions.
Figure C-1. Configuration Flowchart (EQS)
T01617A
SELECT
DEVICE
TYPE
SELECT
MODE
SELECT
SENSOR
TYPE
NUMBER
OF
ELEMENTS
SELECT
OHMS
SELECT
mV
SELECT
RTD
TYPE
NUMBER
OF
WIRES
NUMBER
OF
WIRES
ENGINEERING
UNITS
NUMBER
OF
ELEMENTS
SELECT
THERMOCOUPLE
TYPE
ENTER
CONFIGURATION
ID TAG
ENTER
SECONDARY
UNITS
ENTER SECONDARY
LOWER/UPPER
RANGE VALUES
ENTER
LOWER/UPPER
TEMPERATURE ALARM
OUTPUT
TYPE
ENTER
LOWER/UPPER
RANGE VALUES
SELECT
OUTPUT
ACTION
SELECT
FAIL
MODE
SELECT
INITIALIZE
MODE
STORE
CONFIGURATION
ENTER
DAMPING
SELECT
TRANSMITTER
TYPE
ENTER
CHANNEL
NUMBER
DIGITAL
ABB FSK
ANALOG
T/C
RTD
OHMS
mV
C
O
N
F
I
G
U
R
E