background image

Series 2800 Current to Pressure Transducer

Specifications - Installation and Operating Instructions

Bulletin V-4

The Series 2800 Current to Pressure Transducer

converts a current

input  to  a  linearly  proportional  pneumatic  output  pressure.    This  unit
utilizes  a  closed  loop  pressure  feedback  system  that  closely  controls
output and compensates for vibration, mounting angle, temperature, and
supply pressure variations. These characteristics make this unit ideal for
field  mounting  on  a  valve.  The  control  mechanism  is  a  piezoceramic
actuator  encapsulated  in  a  protective  skin,  which  provides  a  constant
defense against humidity and contaminants. These features make this
unit ideal for use in demanding applications. The 2800 also comes in a
NEMA 4X enclosure and is field reversible. It is FM and CSA approved
intrinsically safe, as well. For ease of installation, this model has input
and  output  ports  on  both  the  front  and  back  and  can  be  easily  panel
mounted.

SPECIFICATIONS
Service:

Oil free, clean dry air filtered to 40 microns.

Input Signal:

4-20 mA.

Air Supply:

Minimum: 5 psig (0.3 bar) above maximum output;

Maximum: 100 psig (6.9 bar).

Output:

3 to 15 psig (0.2 to 1.0 bar), 6 to 30 psig (0.4 to 2.1 bar).

Accuracy:

±0.1% of span.

Hysteresis:

±0.1% of span.

Repeatability:

±0.1% of span.

Deadband:

0.02% of span.

Power Requirement:

Loop powered.

Temperature Limits: 

Operating: -40 to 160°F (-40 to 71°C); Storage: -

40 to 200°F (-40 to 93°C).

Pressure Connections:

1/4˝ female NPT.

Electrical Connection:

1/2˝ female NPT.

Air Consumption:

0.025 scfm (0.01 l/s) at midrange typical.

Output Capacity:

4.5 scfm (2.1 l/s) at 25 psig (1.7 bar) supply; 12.0

scfm (5.7 l/s) at 100 psig (6.9 bar) supply.

Enclosure:

Chromate-treated aluminum with epoxy paint.

Enclosure Rating:

NEMA 4X (IP65) and Intrinsically safe.

Weight:

0.8 lb (0.37 kg).

Agency Approvals:

CSA, CE, FM.

W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.

P.O. BOX 358 • MICHIGAN CITY, INDIANA 46361 U.S.A.

Phone: 219/879-8000

www.dwyer-inst.com

Fax: 219/872-9057

e-mail: [email protected]

Model
2813-WP
2816-WP

Input

4-20 mA
4-20 mA

1

[25.4]

Ø1/8

[Ø3.17]

1-1/2

[38.1]

1-19/64

[33.0]

1-51/64

[45.7]

3-11/16

[93.7]

MOUNTING HOLES

#10-32 UNF-2B X 3/8 DP

2 PLCS

2-3/16

[55.4]

2-15/16

[74.7]

22 GA. WIRE LEADS

APPROX. 18˝ LONG

POS, NEG, GRD

3-1/8

[79.2]

33/64

[13.1]

25/64

[9.72] 49/64

[19.4]

1/2 NPT

Ø1-1/8

[Ø28.7]

IN & OUT PORTS

1/4-18 NPT

4 PLCS

Output

3-15 psig (0.2-1.0 bar)
6-30 psig (0.4-2.1 bar)

Отзывы: