EBTH TEMPERATURE TRANSMITTER
CALIBRATION
B
-
9
METER VALUE ADJUSTMENT
Use this function to adjust the four to 20 milliampere output of the field
device using values from an external current meter. This method is
only valid for HART devices.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
D-TO-A ADJUST
.
Select
METER VALUE ENTRY
.
Use the number keys to enter the current meter
reading.
Use the number keys to enter the current meter
reading.
C A LI-
B R AT E
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
CALIBRATION
→
D-TO-A ADJUST
BENCH CALIB.
E N T E R
D/A CAL USING
UPDOWN ARROW KEYS
→
METER VALUE ENTRY
E N T E R
4 mA CALIBRATION:
ENTER METER VALUE
4.000
E N T E R
20 mA CALIBRATION:
ENTER METER VALUE
20.000
E N T E R
ID TAGNAME
READY