TROUBLESHOOTING
ERROR MESSAGES
5 - 10
FIELD DEVICE
TEMPERATURE
ABOVE LIMIT
- or -
FIELD DEVICE
TEMPERATURE
BELOW LIMIT
BCN
EQN
EQS
TBN
XM/SM/
XE
Field device not calibrated
properly, or transmitter is
at a temperature above
the performance specifi-
cations. Message will not
affect operation but could
mean temperature perfor-
mance is out of range.
Recalibrate the field device. Refer to the
appropriate calibration section for the
device type.
NOTE:
Uncalibrated field devices may have this error
until calibrated.
PTS
Local heat or cold source
exceeds electronics
specifications.
Eliminate or reduce temperature extreme
of the electronics.
FIELD DEVICE
TEMPERATURE
SENSOR FAILURE
BCN
EQN
On-board temperature
sensor failure.
Replace input board. Refer to repair/
replacement section of the appropriate
product instruction.
HIGH PROCESS
ALARM
XM/SM/
XE
Process value over/under
alarm limit.
Correct process problem.
Change alarm value. Refer to
INPUT APPLIED
INCORRECTLY,
CALIBRATION
FAILURE
BCN
EQN
EQS
PTS
TBN
Input signal not at speci-
fied level.
Correct signal and recalibrate. Refer to
the appropriate calibration section for
details.
LOSS OF COIL
EXCITATION
XM/SM/
XE
Coil excitation has
stopped.
Check wiring of excitation signal and ref-
erence signal. If both are OK, call service.
LOW PROCESS
ALARM
XM/SM/
XE
Process value over/under
alarm limit.
Correct process problem.
Change alarm value. Refer to
MAIN POWER WAS
LOST
XM/SM/
XE
Power was lost to device. Check for loose wiring.
Restore totalizers to known values if lost.
NO SMART FIELD
DEVICE
CONFIGURATIONS
PRESENT
STT
No configuration exists in
the STT terminal
memory.
Create configurations. Refer to
NO SMART FIELD
DEVICE RESPONDING
STT
STT terminal not
connected to a device.
Check STT terminal lead connections.
Verify proper field device wiring. Refer to
the installation section of the appropriate
product instruction.
OPTION NOT
INSTALLED
XM/SM/
XE
The current configuration
is calling to use the empty
pipe detector which
requires and optional
board.
Add empty pipe detector option, or turn
empty pipe detection off in the configura-
tion.
OUTPUT PRESSURE
ABOVE LIMIT
AVS
Pressure on output port
01 or 02 is too high.
Check air pressure supply.
POSITION
TRANSMITTER
AVS
The position transmitter
(transducer) has failed.
Refer to the repair/replacement section of
the appropriate positioner product
instruction.
Table 5-2. STT04 Error Messages for ABB FSK Devices
(continued)
Message
Affected
Device
Probable Cause
Corrective Action