TBN580 TRANSMITTER
CALIBRATION
K - 11
D-to-A Adjust
The
D-TO-A ADJUST
selection is only present when you are in the
ANALOG
communication mode, specified in the configuration proce-
dure. This selection allows you to adjust the four to 20 milliampere
output of the field device.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Be sure the control loop is in
manual.
Select
YES
.
Select
D-TO-A ADJUST
.
Use the arrow keys to adjust the 4 mA signal.
NOTE:
When increasing or decreasing the mA sig-
nal, the increments of change increase with succes-
sive depressions until the maximum level of change
is reached. By changing direction you will return to
the smallest increment of change. This adjustment
technique speeds up the adjustment process without
affecting fine adjustment.
Use the arrow keys to adjust the 20 mA signal.
C A LI-
B R AT E
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
CALIBRATION
PROCESS CAL
BENCH CAL pH
BENCH CAL TEMP
→
D-TO-A ADJUST
E N T E R
ADJUST TO 4 mA
THEN HIT ENTER
E N T E R
ADJUST TO 20 mA
THEN HIT ENTER