TB82 TRANSMITTER
CALIBRATION
N - 10
Reset Calibration
This procedure describes how to reset a calibration back to the
default settings.
Key
Display
Comments
This operation will cause a change in output not cor-
responding to the input. Selecting
YES
will hold the
output during calibration.
Select
YES
.
Select
RESET CAL
.
This function sets all process sensor and tempera-
ture sensor calibration data to the default settings.
The following are the factor settings.
Sensor slope: 100 %
Sensor offset: 0 mV
Temperature slope: 1
Temperature offset: 0°C
Select
YES
to reset the calibration.
C A LI-
B R AT E
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
nnnn CAL
TEMP. CAL
EDIT CAL
→
RESET CAL
E N T E R
OUTPUT WILL BE
AFFECTED! PROCEED?
NO
→
YES
E N T E R
ID TAGNAME
READY