XM/SM/XE MAGNETIC FLOWMETER
CREATE/MODIFY CONFIGURATION
I - 4
Enter the calibration factor.
Make a selection using the arrow keys.
Select the engineering units for the totalizer.
Enter the proper pulse factor for the totalization
process.
Enter a value between 0.032 and 2000 ms. For driv-
ing an electromechanical counter, the pulse width
should be about 50 ms. For high speed electronic
devices a pulse width of 0.05 ms. is common.
Enter a value between 0 and 10% of full scale. This
parameter causes the input to drop to a zero state
when the flow drops below the set value.
Make a selection using the arrow keys.
Make a selection using the arrow keys.
Key
Display
Comments
E N T E R
RANGE DN:
n.nnn UNITS
E N T E R
FAIL MODE:
→
LOW
HIGH
E N T E R
SELECT TOT. EU:
→
l
m3
User Defined
E N T E R
PULSE FACTOR:
(0.001 - 1000/EU)
nnn.nn
E N T E R
PULSE WIDTH:
(0.64 - 2000 ms)
nnn.nn
E N T E R
LOW FLOW CUTOFF:
(0 - 10%)
nn.nn%
E N T E R
DIGITAL FILTER:
→
OFF
ON
E N T E R
RANGE CONFIG:
→
2-FWD
1-FWD, 1-REV