EQS TEMPERATURE TRANSMITTER
CREATE/MODIFY CONFIGURATION
C
-
3
Select
LINEAR
.
If
FUNC GENERATOR
is selected, specify 5 input
and output points between 0 and 100%.
Refer to the
Platinum Standard Series Smart Tem-
perature Transmitter EQS
instruction for descrip-
tion.
Enter a value between 0 and 32. Refer to the
Plati-
num Standard Series Smart Temperature Trans-
mitter EQS
instruction for description.
Enter the lower range temperature value and press
. Input the upper range value.
Select an initialization mode using the arrow keys.
Refer to the
Platinum Standard Series Smart Tem-
perature Transmitter EQS
instruction for descrip-
tion.
Select a fail mode using the arrow keys.
Refer to the
Platinum Standard Series Smart Tem-
perature Transmitter EQS
instruction for descrip-
tion.
Enter up to 6 characters. Use familiar units to
describe the output.
To select a character, press the key that has the
desired character. Continue to press the key until the
desired character appears. Use the right arrow key to
move to the next character. Use the left arrow key to
go back to the previous character. Press
when finished.
Input the lower range value and press
.
Input the upper range value.
Key
Display
Comments
E N T E R
OUTPUT TYPE:
→
LINEAR
FUNC GENERATOR
E N T E R
OUTPUT ACTION:
→
NORMAL
REVERSE
E N T E R
DAMPING:
(0-32 SEC)
nn.nn SECS
E N T E R
LOWER RANGE VAL
nn.nn
o
C
UPPER RANGE VAL
nn.nn
o
C
ENTER
E N T E R
INITIALIZE MODE:
→
LOW
HIGH
E N T E R
FAIL MODE:
→
LOW
HIGH
LAST
E N T E R
ENTER
SECONDARY UNITS
nnnnnn
ENTER
E N T E R
SECONDARY L.R.
_nn.nn UNITS
SECONDARY U.R.
nn.nn UNITS
ENTER