L840/MG4
77
11.4 DIP switch/jumper
settings:
The following settings can be defined with the DIP switch:
Switch 1-5:
Address on the XIB security bus
(see addressing)
The panel tamper contact can be bypassed with jumper LK1:
Jumper LK1:
Plugged-in:
Panel tamper not functional
Open:
Panel tamper functional
11.5 Addressing
The circuit module is addressed via a DIP switch.
A maximum of up to 16
circuit modules L840/MG4 can be managed by the panel.
Detector circuit
module L240/MG 2
and L840/MG4 have a common addressing area on the
XIB bus from 1 to 24. Numbering of the circuits is undertaken consecutively
to the addresses of the circuit module (see chapter 10.6 Address table).
Before teaching-in bus motion detectors, all Detector Circuit Modules
L240/MG2 and L840/MG4 must already be logged on!
Example:
Two Detector Circuit Modules L840/MG4, one Detector Circuit Module
L240/MG2 and three bus detector modules are operated on an Intrusion
Alarm Panel L240.
First of all the three circuit modules must be registered.
The panel occupies circuits 1-10.
The first Detector Circuit Module L840/MG4 has an XIB address 01 and
the circuits 11 to 14.
The second Detector Circuit Module L240/MG2 has an XIB address 02
and the circuits 15 to 16.
The third Detector Circuit Module L840/MG4 has an XIB address 03 and
the circuits 17 to 20.
Then the three bus detector modules must be teached-in
(circuits 21-23).
11.6 Commissioning
The plug-in jumper LK1 can be used for bypassing the panel tamper to
suppress the tampering alarm during commissioning (otherwise tamper
alarm).
Jumper LK1 must be removed again after commissioning.
The
installation and connection is undertaken on the panel with the power
switched off.
Screw on the circuit module to the distribution surface in the SAD
enclosure; connect the individual connection cables and detectors in
accordance with the circuit diagram.
Terminate every circuit with a
termination resistor of 2.7 k
Ω
on the last detector.
Set the address on the DIP switch (see chapter 10.6 Address table)
Apply the panel supply.
Logon/Logoff
On the programming level (Engineer menu) select function
“01=Hardware”.
01=System Size
02=Area Opts
The corresponding number (2-digit) should be entered for the circuit
modules.
System Size
Concs-xx