L240/BS
87
Function switch 2-3 “Tamper contact”:
Using function switch 2-3, the cover tamper contact on Evaluation Module
L240/BS can be activated or deactivated. The cover tamper contact must be
activated in VdS approved installations.
OFF (standard setting): The cover tamper contact is operational (tamper
monitoring) and triggers a tampering (sabotage) alarm should the cover
be opened.
ON: The cover tamper contact is non- functional and not operational
(e.g. to suppress a tampering alarm during set-up and commissioning).
Opening the cover will not trigger a tampering alarm.
Function switch 2-4 “Test mode”:
Using function switch 2-4, the Evaluation Module L240/BS can be operated
in test mode.
OFF: Standard mode
ON: Test mode
During operation, the DIP switch should be set to OFF.
Function switch 2-5:
Must be “OFF”.
12.5.3 Address switch
Using the address switch, the Evaluation Module L240/BS connected to the
XIB security bus is addressed. Each Evaluation Module L240/BS has
(independent of the zone) its own address. The address range for the
Evaluation Module L240/BS commences with “1” and must be successive (1,
2, 3, … 8).
Up to 8 Evaluation Modules L240/BS can be connected to the Intrusion
Alarm Panel L240.
Evaluation
module address
Switch
3-1
Switch
3-2
Switch
3-3
Switch
3-4
Switch
3-5
1
OFF OFF OFF OFF OFF
2
ON OFF OFF OFF OFF
3 OFF
ON
OFF
OFF
OFF
4 ON
ON
OFF
OFF
OFF
5
OFF OFF ON OFF OFF
6
ON OFF ON OFF OFF
7
OFF ON ON OFF OFF
8
ON ON ON OFF OFF
Table 1: Addressing