Commissioning
19
If the LED continues to flash, check if
•
address 1 is set on the keypad
•
the
XIB security bus has been correctly connected.
4.3 External connection of
the inputs and outputs
After the panel is ready for operation, the termination resistors or wire
jumpers (links) are removed and the external cables to the detectors, setting
(arming) device and signalling devices are connected.
Connection of the detector circuits:
•
Remove the termination resistor of detector circuit 1 on the terminal block
of the panel. Detector circuit 1 interrupt is displayed after pressing button
5 (display faulty detector) on the keypad.
•
Connect the cable to the detectors (e.g. motion detectors) of circuit 1.
Here, a termination resistor must be connected once at the end of the
cable.
Otherwise, the cable is not monitored.
Only one termination
resistor is allowed for each detector group.
•
If circuit 1 is OK/closed (motion detector does not detect a motion), a
circuit interruption is no longer displayed on the keypad (button 5).
•
Check by inducing a fault on circuit 1 (motion detector detects a motion) if
a fault is detected by the panel and if it is displayed on the keypad.
•
Successively put the other detector groups 2 to 9 into operation in the
same manner as described for circuit 1.
However, circuit 7 (lock detector
circuit) does not require a termination resistor.
An interrupt on circuit 8
(personal attack) and 9 (tampering) must be reset using the Reset
function on the keypad.
•
Connect the setting (arming) device (e.g. contact lock) to circuit 10.
With
the connection of a setting device on the XIB bus (SafeKey Evaluation
Module L240/BS), circuit 10 should be re-programmed to another circuit
type and terminated with the corresponding resistor.
Connection of the signalling device:
•
Remove the terminating resistor for the strobe lights on the terminal block
of the panel (tampering alarm is triggered!).
•
Connect the cable to the ABB strobe light.
The terminating resistor is
already integrated into the strobe lights and connection of an additional
resistor is not necessary.
•
The triggered tamper alarm is reset with the Reset on the keypad.
•
Check the strobe light in the test menu (see chapter 7.1.3 ).
•
Commission both ABB sirens as described with the strobe light.
It is recommended that you only connect both sirens when the Intrusion
Alarm System (incl.
bus modules) is ready to operate.
Telephone dialling device:
•
Remove the wire links of the comm fault and comm alarm (fault signal is
triggered!).
•
Connect the comm fault and comm alarm feedbacks from the telephone
dialling devices.
Panel tamper connection:
•
Remove the wire jumper for the panel tamper (tamper alarm is
triggered!).
•
Connect the connection cable for the panel tamper of the panel.
•
The triggered tamper alarm is reset with the Reset on the keypad
(enclosure must be closed).