Bus Motion Detector
99
13.6 Parameter settings
The detectors have the following factory defaults after teach-in and can be
modified via submenu
“03=Programming”
:
Standard factory settings of the bus motion detectors:
Type designation
Function
IR/XB
IR/XC
EIM/XB
EIM/XC
Cct
nn
nn
nn
nn
Impulses
2
2
1
1
UW TAG
* *
off
off
Anti-Mask
*
on
on
on
Red. range
off
off
off
off
LED red
on
on
on
on
LED yellow
*
on
on
on
LED green
*
*
on
on
AM Sens.
*
on
on
on
Fault
on
on
on
on
Undervoltage
on
on
on
on
Anti stealth
*
*
on
on
Log
off
off
off
off
*not available
The individual parameters are described in the following:
Cct
Cct – nn
Shows the respective circuit of the motion detector. It can be modified
accordingly to another circuit. If it is modified via this parameter, the circuit
type is set in the sub menu “
03=Cct
” of the Engineer menu as
XIB-Det.
Pulses
Pulses – 1/2/3 or hall
This function enables in the set state that the alarm is activated after the
motion detector has triggered 1, 2 or 3 times. The hall function is specially
conceived for the monitoring of narrow halls and enables detection if the hall
is briefly crossed.
UW Tag
UW Tag – on/off
The transmission power of the microwave section is only a few mW and
corresponds roughly with that of a Bluetooth device. However, the Intrusion
Alarm Panel offers the option for switching off the microwave sensors of the
EIM/X detector for unset operation. The microwave anti-masking is also
switched off. When the respective area is set, the microwave sensors are
reactivated. This setting is recommended to reduce the power consumption
of the system.
Anti-mask
Anti-mask – on/off
The anti-mask monitoring is used for detection of deliberate masking or dirt
on the detector. This function is now used in the unset state of the Intrusion
Alarm Panel.
Red. range
Red. range – on/off
The reduction of the circuit range is limited to the detection range of the
detector. This function is useful if the detector is situated in a small area,
where there is an increased risk of false alarms due to the characteristics of
the room.
LED red
LED red – on/off
The red LED indicates the alarm recognition and further displays of the
detector (see chapter 13.3).