Appendix
B
Programming
Example
112
Programming example
In a building, the apartment (area 2/main area) and the office (area 1/lower level) of the owner are located. The
office also has an external access door. It is necessary to ensure that the building alarm can only be set if the office
has been set beforehand. Should the building intruder alarm be disarmed, the office will remain set.
In the office, the window is monitored with a magnetic reed contact and glass break sensor (1 x Detector Circuit
Module, 2-fold L240/MG2). Furthermore, the area is monitored with a Motion Detector IR/B L240/IR-XB. Setting is
performed with a SafeKey Evaluation Module L240/BS. A Keypad L240/PT is located in the room for operation and
display.
In the apartment, the window is monitored with a magnetic reed contact and glass break sensor (2 x Detector
Circuit Module, 2-fold L240/MG2 and 2 x Detector Circuit Module, 4-fold L840/MG4). Two Motion Detectors
L240/IR/XB monitor the hallways. Setting is performed with a SafeKey Evaluation Module L240/BS. Operation and
display is undertaken with two Keypads L240/PT.
Addressing:
The bus modules are addressed as follows using DIP switches/jumpers:
Type
XIB address
L240/MG2 office
Detector module
01
L240/MG2 apartment 1
Detector module
02
L240/MG2 apartment 2
Detector module
03
L840/MG4 apartment 3
Detector module
04
L840/MG4 apartment 4
Detector module
05
L240/PT office
Keypad
1
L240/PT apartment 1
Keypad
2
L240/PT apartment 2
Keypad
3
L240/BS office
Evaluation module
01
L240/BS apartment
Evaluation module
02
Programming:
Access to the Edit level with the Engineer PIN (see chapter 7).
In menu item “
01=System Size
” register the number of bus devices:
System Size
Areas-2
Press button
2
Concs-05
Press button
0
and
5
L240/B/BS-02
Press button
0
and
2
Keypads-3
Press button
3
SM-2
Press button
2