L240/MG2
72
On both left terminals the circuit input (evaluation) is connected, both the
middle terminals are used for connection terminals and the termination
resistor is integrated into both of the right terminals.
The number of the circuit is on the left beside the DIP switch followed by the
number of the circuit on the right beside the XIB terminal block.
Example:
The detector circuit module is registered on the panel.
The panel occupies
circuits 1-10; on the circuit module circuit 11 is located on the right beside
the XIB terminal block, and circuit 12 on the left beside the DIP switch.
C on n ec tio n o f 2 se ns o rs:
Bo th m idd le con tacts are sim ply us ed as
intercon ne ction term ina ls.
C
ct t
e
rm
in
ati
on
re
sis
tor
(a
va
ila
ble
o
n c
irc
uit
bo
ard
)
Cc
t input
C o nn e c tio n o f a s e n s o r :
B oth m idd le contacts rem ain
free.
Cct t
erm
inat
ion resistor
(avai
lable
on
c
ircui
t
board)
Cct i
n
p
u
t
10.3 Description of the inputs and outputs
Terminal block
Function
Description
CN2
Output for the supply voltage of detectors
Protected by fuse F1 with 100 mA
+
-
A
B
XIB security bus
Supply v 12 V
0 V
Data line A
Data line B
CN1 and CN3
Detector circuits, freely programmable
Every detector group must be terminated with the
integrated 2.7k Ohm resistor in the normal state
Red LED
Display tamper contact/circuit fault
ON
:
Tamper alarm (tamper contact is triggered) or at least
one detector group faulty
OFF
:
Tamper contact not triggered or monitoring
deactivated:
LED green
Operation
ON:
Module not logged on
Flashes (1 Hz):
Module logged on
10.4 Addressing
The circuit module is addressed via a DIP switch.
A maximum of up to 24 circuit modules L240/MG2 can be managed by the
panel.
The Detector Circuit Modules L240/MG2 and L840/MG4 have a
common addressing range on the XIB bus from 1 to 24. Numbering of the
circuit is undertaken consecutively to the addresses of the circuit module.
Before teaching-in bus motion detectors, all Detector Circuit Modules
L240/MG2 and L840/MG4 must be logged on!
Note:
Cable entry for both circuits is on the
same side. The circuit input is on the
left, the termination resistor on the
right.
Cct
2 sensor
connected
Cct
1 sensor
connected
XIB