Configuration and Programming by the Engineer
57
Area assigned to the circuit (only if circuit = EIB/KNX).
Int Set Off
Circuit-0xx
Int Set Off-Off
0=Off
; 1=On
The enable for shutdown of a circuit with internal setting is provided.
The shut down then occurs in access level 0 or 1.
Off:
The circuit cannot by switched off and is active with internal or
external setting (delivery state of circuits 4-6).
On:
The circuit (e.g. motion detector) can be switched off for internal
setting (delivery state of circuit 1-3) and is thus inactive with internal
setting.
Ext Set Off
Circuit-0xx
Ext Set Off-Off
0=Off
; 1=On
VdS
The enable for shutdown of a circuit with external setting is provided.
The
shut down then occurs in access level 0 or 1.
Off:
The circuit cannot by switched off and is active with internal or
external setting.
On:
The circuit can be switched off for external setting and is thus
inactive with external setting (completely inactive).
Silent Alarm
Circuit-0xx
Silent Alarm-Off
0=Off
; 1=On
On an alarm (intrusion or personal attack), triggering of the local alerting
devices (sirens and strobes) can be prevented.
Off:
Local alerting is triggered.
On:
Local alerting is not triggered but rather a silent alarm (output
“Intrusion” or “Personal attack”) is triggered.
If a dialling device (comm)
cannot send the silent alarm, a negative acknowledgement is displayed
on the input “Comm alarm”, and local alerting is actuated.
Print Unset
Circuit -0xx
Print Unset-Off
0=Off
; 1=On
The error and text messages from intrusion circuits can also be printed in the
unset state via the serial interface L208/V.24 and registered in the event log
(e.g. for test purposes).
Off:
No print out and registration of the messages.
On:
The circuit messages are printed out and registered
.
Pulse
Circuit -0xx
Pulse-On
0=Off;
1=On
On personal attack circuits, the assigned outputs (e.g. “Personal attack“) can
be controlled statically or by a pulse.
Off:
The outputs switch statically until a reset.
On:
The outputs can only be controlled for the duration of the set alarm
time.