L240/MG2
75
10.6 Address table L240/MG 2
and L840/MG 4
Using the address switch the Detector Circuit Modules L240/MG2 and
L840/MG4 are addressed on the XIB security bus.
Each circuit module has
(independently of the area) its own address.
The address area for each
module type commences with “1” and must be successive (1, 2, 3, … 24).
A maximum of up to 24 circuit modules can be managed by the panel
(L240/MG2 or L840/MG4 – or combined).
Of these, only a maximum of 16
circuits may be detector circuit modules L840/MG4!
With the number of detector circuits L240/MG2 or L840/MG4 and bus motion
detector modules, it is important to observe that the total number of detector
circuits does not exceed 80.
Address
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
1
OFF
OFF
OFF
OFF
OFF
2
ON
OFF
OFF
OFF
OFF
3
OFF
ON
OFF
OFF
OFF
4
ON
ON
OFF
OFF
OFF
5
OFF
OFF
ON
OFF
OFF
6
ON
OFF
ON
OFF
OFF
7
OFF
ON
ON
OFF
OFF
8
ON
ON
ON
OFF
OFF
9
OFF
OFF
OFF
ON
OFF
10
ON
OFF
OFF
ON
OFF
11
OFF
ON
OFF
ON
OFF
12
ON
ON
OFF
ON
OFF
13
OFF
OFF
ON
ON
OFF
14
ON
OFF
ON
ON
OFF
15
OFF
ON
ON
ON
OFF
16
ON
ON
ON
ON
OFF
17
OFF
OFF
OFF
OFF
ON
18
ON
OFF
OFF
OFF
ON
19
OFF
ON
OFF
OFF
ON
20
ON
ON
OFF
OFF
ON
21
OFF
OFF
ON
OFF
ON
22
ON
OFF
ON
OFF
ON
23
OFF
ON
ON
OFF
ON
24
ON
ON
ON
OFF
ON
10.7 Technical data
Supply voltage
12 V DC, via the XIB security bus
Current consumption
15 mA
Connections
XIB:
Plug-in screw terminals
Detector groups:
Insulation piercing terminals
(LSA strips)
Ambient temperature
Operation 0°C …
55 °C
Environmental class
II
Design
PCB with supporting ring and enclosure cover
Installation
In a standard 55 mm switch socket
Dimensions
70 x 70 x 25 mm (H x W x D)
Weight
0.25 kg
CE mark
In accordance with the EMC guideline and low
voltage guideline
VdS No.
In preparation