HVC
‐
PD
E
‐
Bus
Charger
Installation
Guide
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022 Page
77
of
146
5.8.3. Connect the Interlock cable for the HVC 150 kW system
Interlock cable connection in the
primary
HVC 150
:
A Terminal
block
B Interlock
cable
from/to
ACS Control Module (ACM)
1. Move the cable towards the terminal block (A).
2. Strip 0.43 Inch of the insulation from the ends of
only the White and Brown wire!
3. Crimp a ferrule onto the end of the White and Brown wire.
4. Ensure that the unused wires, the Green and Yellow wire, are protected so that they
cannot touch metal parts.
5. Make a wire connection between pin X286-6 and X286-7 and pin X286-10 and X286-11.
6. Loosen the connector screws.
7. Insert the wires into the connectors, see table below:
Functional description
Connector
Wire number
Interlock In
X286-15
Brown
Interlock Out
X286-14
White
Interlock GND
X286
Shield
Interlock loop
X286-6
Black
Interlock loop
X286-7
Black
Interlock loop
X286-10
Black
Interlock loop
X286-11
Black
See also Appendix H
Signal connection diagram
.
8. Tighten the connector screws with a tightening torque of 1.0 ft-lb.