The HVC 150(S) has air inlets (A) on all sides and air outlet (B) on the front to control the
temperature inside the cabinet. Do not install any objects near these air inlets and outlets (see
also Caution above). If necessary, take precautions to prevent snow, sand or dust from
blocking the inlets and outlets.
Specifications for inside installation of the Power Cabinet
Airflow required for one cabinet = 853.44 CFM.
Maximum allowed pressure drop = 0,0435113 PSI. If the pressure drop of the room is higher
than 0,0435113 PSI an extra fan should be placed.