HVC
‐
PD
E
‐
Bus
Charger
Installation
Guide
Document: V1.2 / Document No.: 6AGA000008-0629-EN | Date: 06-30-2022 Page
30
of
146
When placing multiple HVC 150 systems, it is necessary to take the following into account:
Cabinets can be placed side-by-side;
Cabinets can be placed back-to-back with 7.87 Inch distance (2x 3.94 Inch) or when
the sides are free with 0 Inch distance;
Door on front side must be kept accessible (recommended 47.24 Inch);
See
also
Required space for the Power Cabinet
on Page 28.
3.5.3. Required space for the Charge pole
The Charge Pole requires a space of 57.91 x 49.80 Inch. This space is calculated as follows:
An Charge Pole footprint of 41.95 x 14.61 Inch.
The following free space:
7.87 Inch at the rear side.
3.94 Inch at the left side.
3.94 Inch at the right side.
35.43 Inch at the front side to open the door.
A Column
B Mast
boom