![ABB FSPS-21 Скачать руководство пользователя страница 91](http://html.mh-extra.com/html/abb/fsps-21/fsps-21_user-manual_2729091.webp)
IP
and
UDP
fields contain the IP address of the source and the destination as well as the
communication ports and length of the message.
RPC
contains, for example, the read or write service ID, interface description and selected
objects.
NDR
request block describes the length of the following data block. The response block
also contains bytes ErrorCode, ErrorDecode, ErrorCode1 and ErrorCode2 for presenting
the status of the request. The response error codes are listed in the table below.
Value and meaning
Byte
0xDF (Error Write)
ErrorCode
0xDE (Error Read)
0x80 (PNIORW) ErrorCode1 decoded as shown in section
. Error-
Code2 is 0.
ErrorDecode
0x81 (PNIO) ErrorCode1 and ErrorCode2 decoded as shown in section
.
Error class and error code. See section
ErrorCode1
Not described here
ErrorCode2
ErrorCode1
The table below lists the ErrorCode1 with PNIORW decoding.
PROFINET IO – Communication protocol 73
ErrorCode1
The table below lists the ErrorCode1 with PNIORW decoding.
Error class
Meaning
Error code
0…9
(Reserved)
10 (0x0A)
Application
0 = Read error
1 = Write error
2 = Module failure
3…7 = Reserved
8 = Version conflict
9 = Feature not supported
10…15 = User-specific
11 (0x0B)
Access
0 = Invalid index
1 = Write length error
2 = Invalid slot
3 = Type conflict
4 = Invalid area
5 = State conflict
6 = Access denied
7 = Invalid range
8 = Invalid parameter
9 = Invalid type
10…15 = User-specific
12 (0x0C)
Resource
0 = Read constraint conflict
1 = Write constraint conflict
2 = Resource busy
3 = Resource unavailable
4…7 = Reserved
8…15 = User-specific
13…15
User-specific
x
x
x
x
x
x
x
x
MSB LSB
ErrorCode1.pdf
Error code
Meaning
Error class
(Reserved)
0…9
0 = Read error
1 = Write error
2 = Module failure
3…7 = Reserved
8 = Version conflict
9 = Feature not supported
10…15 = User-specific
Application
10 (0x0A)
0 = Invalid index
1 = Write length error
2 = Invalid slot
3 = Type conflict
4 = Invalid area
5 = State conflict
6 = Access denied
7 = Invalid range
8 = Invalid parameter
9 = Invalid type
10…15 = User-specific
Access
11 (0x0B)
PROFINET IO – Communication protocol 91
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......