Module parameters are automatically saved in the drive, there is no need to make a
manual back-up.
2.
Disconnect the supply with the supply disconnecting device.
WARNING!
Read and obey the instructions in chapter
and
chapter
Safety instructions
in the drive hardware manual. If you ignore them,
injury or death, or damage to the equipment can occur.
3.
Remove the wiring and the FSPS-21 module.
4.
Mark clearly on the FSPS-21 module that it is decommissioned.
5.
Install the new FSPS-21 module and wiring according to chapter
Installation
.
6.
Re-configure the HW configuration in the PLC project.
7.
Perform the start-up procedure according to chapter Start-up.
8.
Perform the validation procedure for each safety function according to chapter Verification
and validation.
9.
Update the revision of the new FSPS-21 module to the logbook of the driven machine.
Drive replacement
If you have to replace the drive where the FSPS-21 module is installed, for example, because
of a serious drive failure, follow the procedure below.
■
Reinstalling the FSPS-21 module to another drive
1.
Stop the driven machinery and prevent an unexpected start-up.
2.
Make a backup file of the drive parameters before drive replacement.
You can make a backup of the drive configuration using the control panel or the Drive
composer PC tool. See applicable drive FW manual, Control panel manual, or Drive
composer manual.
3.
Disconnect the supply with the supply disconnecting device.
WARNING!
Read and obey the instructions in chapter
and
chapter
Safety instructions
in the drive hardware manual. If you ignore them,
injury or death, or damage to the equipment can occur.
4.
Remove the wiring and the FSPS-21 module.
5.
Install the new drive. See the drive hardware manual.
6.
Install the FSPS-21 module and wiring to the new drive according to chapters
and .
7.
Make the necessary parameter settings according to chapter
, or restore
the parameters from the backup file. See applicable drive FW manual, Control panel
manual, or Drive composer manual.
8.
Perform the start-up procedure according to chapter
.
9.
Perform the validation procedure for each safety function according to chapter
.
Note:
The STO function is the basic safety function and it has to be validated first.
Maintenance 189
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......