STATE/Description
Value
Name
Bit
Positioning mode
Speed control mode
OFF2 inactive
1
OFF_2_STA
4
OFF2 ACTIVE
0
OFF3 inactive
1
OFF_3_STA
5
OFF3 ACTIVE
0
SWITCH-ON INHIBIT ACTIVE
1
SWC_ON_ INHIB
6
SWITCH-ON INHIBIT NOT ACTIVE
0
Warning/Alarm
1
ALARM
7
No Warning/Alarm
0
OPERATING
. Actual value equals reference value (= is
within tolerance limits).
1
AT_SETPOINT
8
Actual value differs from reference value (= is outside toler-
ance limits).
0
Automation system is requested to assume control.
1
REMOTE
9
Control by automation system is not possible. Control is
possible only at the device or by another interface.
0
Target position reached.
Actual frequency or speed
value equals or is greater than
supervision limit.
1
10
Not at target position
Actual frequency or speed
value is within supervision
limit.
0
Homing procedure was ex-
ecuted and is valid.
Mapped to PROFIdrive SW
bit 11.
1
11
Vendor-specific bit as defined
by PROFIdrive parameter
939.
No valid home position avail-
able.
0
As default mapped to
PROFIdrive SW bit 11.
Traversing task acknowledge-
ment (0 → 1)
Mapped to PROFIdrive SW
bit 11.
1
12
0
Vendor-specific bit as defined
by PROFIdrive parameter
940.
As default mapped to
PROFIdrive SW bit 12.
Drive stopped.
Mapped to PROFIdrive SW
bit 11.
1
13
Drive moving. Traversing task
is executed (n <> 0).
0
Vendor-specific bit as defined
by PROFIdrive parameter
941.
As default mapped to
PROFIdrive SW bit 13.
Vendor-specific bit as defined by PROFIdrive parameter 942.
14
As default mapped to PROFIdrive SW bit 14.
PROFINET IO – Communication profiles 77
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......