Configuring the master station
After the adapter module has been initialized by the drive, you must prepare the master
station for communication with the module. For FSPS-21, see
If you are using another master system, refer to its documentation for more
information.
Media Redundancy Protocol (MRP)
The Media Redundancy Protocol (MRP) network uses ring topology that includes multiple
nodes as shown in the connection diagram below. One of the nodes has the Media
Redundancy Manager (MRM) role and the nodes with FSPS-21 module(s) have the role of
Media Redundancy Clients (MRC). Each node, MRM or MRC, has a pair of ports for
connecting in the ring.
For FSPS-21 module, the link speed of both ports is 100 Mbit/s, full duplex.
Note:
The number of nodes in the ring should not exceed 50 nodes.
Port 2
Port 1
PLC or
switch MRM
ABB drive
ABB drive
1
3
2
1
...
...
4
Description
No.
ABB drive equipped with FSPS-21 module
1
PLC or switch with MRM (Media Redundancy Manager)
2
Port 1
3
Port 2
4
■
Configuring Media Redundancy Protocol (MRP) with Siemens PLC
You can configure MRP for Siemens PLC with SIMATIC S7 after setting the basic
configuration. For instructions on basic configuration, see section
SIMATIC Fail-safe S7 PLC (page 149)
1.
Double-click PN-IO in the station window.
60 PROFINET IO – Start-up
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......