Default
Description
Name/Value
No.
N/A
Read-only
. Displays the parameter table revision of
the fieldbus adapter module mapping file stored in the
memory of the drive. In format
xyz
, where
x
= major revision number
y
= minor revision number
z
= correction number
OR
in format
axyz
, where
a
= major revision number
xy
= minor revision numbers
z
= correction number or letter.
FBA A/B par table ver
28
Parameter table revision
N/A
Read-only
. Displays the drive type code of the fieldbus
adapter module mapping file stored in the memory of
the drive.
FBA A/B drive type
code
29
Drive type code of the fieldbus adapter module map-
ping file
N/A
Read-only
. Displays the fieldbus adapter module
mapping file revision stored in the memory of the drive
in decimal format.
FBA A/B mapping file
ver
30
Mapping file revision
0
= Idle
or
4
= Offline
Read-only
. Displays the status of the fieldbus adapter
module communication.
Note:
The value names may vary by drive.
D2FBA A/B comm
status
31
Note:
Only active drive-controlled channel will change
comm status
online
. PROFIsafe alone will not change
the comm status.
Adapter is not configured
0
= Idle
Adapter is initializing.
1
= Exec.init
A timeout has occurred in the communication between
the adapter and the drive.
2
= Time out
There is an internal error in the communication
between the adapter and the drive. Contact your local
ABB representative.
3
= Conf.err
Adapter is off-line
4
= Off-line
Adapter is on-line
5
= On-line
Adapter is performing a hardware reset.
6
= Reset
N/A
Read-only.
Displays patch and build numbers of the
adapter module's firmware version in
xxyy
format,
where:
FBA A/B comm SW
ver
32
xx
= patch number
yy
= build number.
Example: If the firmware version (<ma-
jor>.<minor>.<patch>.<build>) is 3.10.200.13, the value
C80D is displayed. If the version is 3.10.0.0, the value
0 is displayed.
See also parameter 33.
PROFINET IO – Start-up 53
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......