References in speed control mode
In the speed control mode, references are 16-bit or 32-bit words containing a sign bit and
a 15-bit or 31-bit integer. A negative reference (indicating reversed direction of rotation) is
formed by calculating the two’s complement from the corresponding positive reference.
A 16-bit speed reference (REF or NSOLL_A) in hexadecimal (0…4000h) corresponds to
0…100% of Maximum Reference (as defined with a drive parameter).
A 32-bit speed reference (NSOLL_B) in hexadecimal (0…4000 0000h) corresponds to
0…100% of Maximum Reference (as defined with a drive parameter).
■
Actual values
Actual values are 16-bit or 32-bit words containing information on the operation of the drive.
The functions to be monitored are selected with a drive parameter.
Actual values in speed control mode
The scaling of 16-bit actual speed values (ACT or NIST_A) in hexadecimal (0…4000h)
corresponds to 0…100% of the maximum reference (as defined with a drive parameter, for
example, speed scaling in ACS580 and ACS880).
The scaling of 32-bit actual speed values (NIST_B) in hexadecimal (0…4000 0000h)
corresponds to 0…100% of the maximum reference (as defined with a drive parameter, for
example, speed scaling in ACS580 and ACS880.
ABB Drives communication profile
■
Control word and Status word
The Control word is the principal means for controlling the drive from a fieldbus system. It
is sent by the fieldbus master station to the drive through the adapter module. The drive
switches between its states according to the bit-coded instructions in the Control word and
returns status information to the master in the Status word.
The contents of the Control word and the Status word are detailed below. The drive states
are presented on page
.
Control word contents
The table below shows the contents of the Control word for the ABB Drives communication
profile. The upper case boldface text refers to the states shown on page
STATE/Description
Value
Name
Bit
Proceed to
READY TO OPERATE
.
1
OFF1_ CONTROL
0
Stop along currently active deceleration ramp. Proceed to
OFF1
ACTIVE
; proceed to
READY TO SWITCH ON
unless other inter-
locks (OFF2, OFF3) are active.
0
Continue operation (OFF2 inactive).
1
OFF2_ CONTROL
1
Emergency OFF, coast to stop. Proceed to
OFF2 ACTIVE
, pro-
ceed to
SWITCH-ON INHIBITED
.
0
80 PROFINET IO – Communication profiles
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......