Description
FSPS-21 settings are stored in the drive parameters and also in the configuration files.
FSPS-21 configuration parameters are included in the backup of the drive parameters.
■
Settings for backup
Consider the following points:
•
Backup is not slot-specific. For example, backup in FBA A, slot 1 of the control unit can
be restored to FBA A, slot 2.
•
Backup depends on the fieldbus channel. For example, backup of FSPS-21 in FBA A
is not restored to FSPS-21 in FBA B.
Configuration backup for FSPS-21
Backup includes the following configuration for PROFINET IO in FSPS-21:
Configuration
Sets the station name using DCP. See
.
Station name
When set, backup will automatically include this config-
uration.
Writable strings for identification and maintenance.
See
I&M 1-3
When set, backup will automatically include this config-
uration.
PROFIdrive CW and SW user bit mapping. See
PROFIdrive parameters (page 201)
PROFIdrive parameters 934-943
Note:
Backup will include this configuration only when it is
stored with PROFIdrive parameter 971.
Writable SNMP MIB-2 string.
System location
When set, backup will automatically include this config-
uration.
System name
System contact
The settings are saved to the drive after 10 seconds. If a Refresh command is given to
FSPS-21 using parameter 51.27, the pending backup is transferred to drive immediately
and FSPS-21 is rebooted after the transfer is completed.
Note:
The new setting is not saved to drive if the drive was powered off or the adapter was
disconnected from the drive within 10 seconds of changing a setting.
FSPS-21 module replacement
If the FSPS-21 module fails to operate, you have to replace it with a new one; you cannot
repair the module.
■
Replacing the FSPS-21 module
1.
Stop the driven machinery and prevent an unexpected start-up.
188 Maintenance
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......