Example
value
Description
Name/Value
Index
Selects one of the PNIO profiles.
FBA A/B PAR2
(PROTOCOL/ PRO-
FILE)
51/54.02
11
Profile PNIO ABB Pro is selected
PNIO ABB Pro
Sets the Ethernet communication rate.
FBA A/B PAR2
(COMMRATE )
51/54.03
0
Ethernet communication rate is negotiated automat-
ically by the device.
Auto
Static IP
The user can set the IP configuration for the network
in these parameters or in the PLC project.
IP CONFIGURA-
TION
51/54.04 ... 13
0
Shows the telegram type for the selected I/O com-
munication.
Telegram type
51/54.20
This parameter is read-only.
4
PPO Type 4
PPO4
Enables/disables the sending of diagnostic mes-
sages to the PROFINET network.
Diagnostic alarm
51/54.21
0
Diagnostic messages are sent.
Enabled
1
Sets the PROFIsafe destination address, that is, the
address of the FSPS-21 module in the safety com-
munication network.
F Destination Ad-
dress
51/54.24
This address must be the same as is set in the F-
Parameters for the PROFIsafe module properties
(F_Dest_Add).
12
Allows defining the PROFINET station name.
PN Name Index
51/54.25
By default this value is 0 and the station name is set
in PLC project. When the value is set to other than
0, the PROFINET station name is overwritten in the
format “abbdrive-xx”, where xx is the value of the
parameter name index.
Example: Setting this value to 12 results in the name
“abbdrive-12”.
Note:
During every boot the FSPS-21 module checks the
value of PN Name Index:
• If the value is not Zero then the active PN Name
Index overrides the PROFINET station name.
• If the new name is set by DCP Set command as
permanent, the new name is used and stored to
flash. The PN Name Index parameter value is not
changed, so after next boot, the name is taken
according to the PN Name Index.
• If the new name is set by DCP Set command as
temporary, the new name is used and the empty
name is stored to flash. The PN Name Index
parameter value is not changed, so after next boot,
the name is taken according to the PN Name In-
dex.
• The PROFINET DCP factory reset also resets the
PN Name Index value to default (0).
PROFIsafe 125
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......