TABLE 3-1 –R410-A PRESSURE / TEMPERATURE CHART
PSIG
TEMP
˚
F
PSIG
TEMP
˚
F
0
-60
78
20
2
-58
80
21
4
-54
85
24
6
-50
90
26
8
-46
95
29
10
-42
100
32
12
-39
105
34
14
-36
110
36
16
-33
115
39
18
-30
120
41
20
-28
125
43
22
-26
130
45
24
-24
135
47
26
-20
140
49
28
-18
145
51
30
-16
150
53
32
-14
160
57
34
-12
170
60
36
-10
180
64
38
-8
190
67
40
-6
200
70
42
-4
210
73
44
-3
220
76
46
-2
225
78
48
0
235
80
50
1
245
83
52
3
255
85
54
4
265
88
56
6
275
90
58
7
285
92
60
8
295
95
62
10
305
97
64
11
325
101
66
13
355
108
68
14
375
112
70
15
405
118
72
16
500
134
74
17
600
149
76
19
700
159
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...