ELECTRICAL DATA
ELECTRICAL SERVICE SIZING
In order to use the electrical service required for
the cooling only eco2 rooftop, use the appropriate
calculations listed below from U.L. 1995. Based on the
confi guration of the rooftop, the calculations will yield
different MCA (minimum circuit ampacity), and MOP
(maximum overcurrent protection).
Using the following load defi nitions and calculations,
determine the correct electrical sizing for your unit. All
concurrent load conditions must be considered in the
calculations, and you must use the highest value for any
combination of loads.
Load Defi nitions:
•
LOAD1
is the current of the largest motor – com-
pressor or fan motor.
•
LOAD2
is the sum of the remaining motor cur-
rents that may run concurrently with LOAD1.
•
LOAD3
is the current of the electric heaters
– zero for cooling only units.
•
LOAD4
is the sum of any remaining currents
greater than or equal to 1.0 amp.
Use the following calculations to determine MCA
and MOP for units supplied with a single-point power
connection:
MCA = (1.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
MOP = (2.25 x LOAD1) + LOAD2 + LOAD3 + LOAD4
If the MOP does not equal a standard current rating
of an overcurrent protective device, then the marked
maximum rating is to be the next lower standard rating.
However, if the device selected for MOP is less than the
MCA, then select the lowest standard maximum fuse
size greater than or equal to the MCA.
TABLE 2-7 – COMPRESSOR DATA - R410A
MODEL
MODEL
NOMINAL VOLTAGE
208-230/3/60
460/3/60
575/3/60
RLA*
LRA
RLA*
LRA
RLA*
LRA
050
1A
ZP120
33.3
239
17.9
125
12.8
80
1B
ZP137
48.0
245
18.6
125
14.7
100
2A
ZP121
33.3
239
17.9
125
12.8
80
2B
ZP137
48.0
245
18.6
125
14.7
100
051
1A
ZP137
48.0
245
18.6
125
14.7
100
1B
ZP137
48.0
245
18.6
125
14.7
100
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP137
48.0
245
18.6
125
14.7
100
060
1A
ZP137
48.0
245
18.6
125
14.7
100
1B
ZP182
55.7
340
26.9
172
23.7
132
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP182
55.7
340
26.9
172
23.7
132
061
1A
ZP154
51.3
300
22.4
150
19.8
109
1B
ZP182
55.7
340
25.0
172
23.7
132
2A
ZP137
48.0
245
18.6
125
14.7
100
2B
ZP182
55.7
340
25.0
172
23.7
132
TABLE 2-8 – POWER SUPPLY VOLTAGE LIMITS
POWER SUPPLY
MINIMUM VOLTAGE
MAXIMUM VOLTAGE
208/230V/3PH/60HZ
187
253
460V/3PH/60HZ
414
506
575V/3PH/60HZ
518
632
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...