Parameter Description and Options
TABLE 7-1 – DEFINITIONS (CONTINUED)
Continued on next page
MENU ITEM
DEFINITION
HEAT 1 MIN RUN TIMER
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME
TIMER FOR HEAT SECTION 1 IN SECONDS
HEAT 2 (W2)
THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W2
- SECOND STAGE HEATING
HEAT 2 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR
HEAT SECTION 2 IN SECONDS.
HEAT 2 MIN RUN TIMER
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME
TIMER FOR HEAT SECTION 2 IN SECONDS
HEAT 3 (W3)
THIS IS THE STATUS OF THE BINARY INPUT TO TERMINAL W3
- THIRD STAGE HEATING
HEAT 3 ASCD TIMER
THIS GIVES THE ACTUAL TIME OF THE OFF CYCLE TIMER FOR
HEAT SECTION 3 IN SECONDS.
HEAT 3 MIN RUN TIMER
THIS GIVES THE ACTUAL TIME OF THE MINIMUM RUN TIME
TIMER FOR HEAT SECTION 3 IN SECONDS
HEAT FAN OFF DELAY
IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY
BETWEEN THE TIME THE HEAT CALL IS TERMINATED AND THE
SHUT DOWN OF THE SUPPLY FAN
HEAT FAN ON DELAY
IN THE INTERMITTENT FAN MODE THIS IS THE TIME DELAY
BETWEEN THE TIME THE HEATING OPERATION IS VERIFIED
AND THE START OF SUPPLY FAN OPERATION
HEATING MODE ENABLED FOR OPERATION
THIS PARAMETER MUST BE TURNED ON TO ALLOW HEATING
OPERATION
HEATING NUMBER #1 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 1 HAS
BEEN OPERATIVE
HEATING NUMBER #2 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 2 HAS
BEEN OPERATIVE
HEATING NUMBER #3 ACCUMULATED RUNTIME
THIS IS THE NUMBER OF HOURS THAT HEATING SYSTEM 3 HAS
BEEN OPERATIVE
HEATING OUTPUT #1 (H1)
THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT
CONTROLLER TO HEAT SECTION # 1, OFF/ON
HEATING OUTPUT #2 (H2)
THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT
CONTROLLER TO HEAT SECTION # 2, OFF/ON
HEATING OUTPUT #3 (H3)
THIS IS THE STATUS OF THE BINARY OUTPUT FROM THE UNIT
CONTROLLER TO HEAT SECTION # 3, OFF/ON
HOT GAS PRESENT ON COMPRESSOR # 1
THIS PARAMETER MUST BE TURNED ON WHEN HOT GAS
BYPASS IS INSTALLED
HOT GAS REHEAT
THIS PARAMETER WOULD BE TURNED ON TO ENABLE HOT GAS
REHEAT. THIS FEATURE IS NOT AVAILABLE ON THESE UNITS
HOT WATER VALVE OUTPUT STATUS
THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER
OUTPUT TO THE HYDRONIC VALVE IN %
HOT WATER VALVE OUTPUT STATUS
(REVERSE ACTING)
THIS GIVES THE STATUS OF THE ANALOG UNIT CONTROLLER
OUTPUT TO THE HYDRONIC VALVE IN % WHEN THE UNIT IS
PROGRAMMED FOR A REVERSE ACTING VALVE
HOUR
THIS PARAMETER IS USED TO ENTER THE HOUR OF THE
CURRENT TIME BASED ON A 24 HOUR SCHEDULE, 13 WOULD
BE 1 PM
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...