136
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
Continued on next page
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
71 H - 73 L
113 H
- 115 L
NA
NA
NA
HOLIDAY #5 (SAME FORMAT AS HOLIDAY #1)
74 H - 76L
116 H
- 118 L
NA
NA
NA
HOLIDAY #6 (SAME FORMAT AS HOLIDAY #1)
77 H - 79 L
119 H
- 121 L
NA
NA
NA
HOLIDAY #7 (SAME FORMAT AS HOLIDAY #1)
7A H - 7C
L
122 H
- 124 L
NA
NA
NA
HOLIDAY #8 (SAME FORMAT AS HOLIDAY #1)
7D H
- 7F L
125 H
- 127 L
NA
NA
NA
HOLIDAY #9 (SAME FORMAT AS HOLIDAY #1)
80 H - 82 L
128 H
- 130 L
NA
NA
NA
HOLIDAY #10 (SAME FORMAT AS HOLIDAY #1)
83 H - 85 L
131 H
- 133 L
NA
NA
NA
HOLIDAY #11 (SAME FORMAT AS HOLIDAY #1)
86 H - 88 L
134 H
- 136 L
NA
NA
NA
HOLIDAY #12 (SAME FORMAT AS HOLIDAY #1)
89 H - 8B
L
137 H
- 139 L
NA
NA
NA
HOLIDAY #13 (SAME FORMAT AS HOLIDAY #1)
8C H
- 8E L
140 H
- 142 L
NA
NA
NA
HOLIDAY #14 (SAME FORMAT AS HOLIDAY #1)
8F H - 91
L
143 H
- 145 L
NA
NA
NA
HOLIDAY #15 (SAME FORMAT AS HOLIDAY #1)
92 H - 94 L
146 H
- 148 L
NA
NA
NA
HOLIDAY #16 (SAME FORMAT AS HOLIDAY #1)
95 H - 97 L
149 H
- 151 L
NA
NA
NA
HOLIDAY #17 (SAME FORMAT AS HOLIDAY #1)
98 H - 9A
L
152 H
- 154 L
NA
NA
NA
HOLIDAY #18 (SAME FORMAT AS HOLIDAY #1)
9B H - 9D
L
155 H
- 157 L
NA
NA
NA
HOLIDAY #19 (SAME FORMAT AS HOLIDAY #1)
9E H - A0L
158 H
- 160 L
NA
NA
NA
HOLIDAY #20 (SAME FORMAT AS HOLIDAY #1)
A1 H
161 H
-
0
255
SUPPLY AIR TEMPERATURE (1/10 DEGREES, HIGH BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
A1 L
161 L
-
0
255
SUPPLY AIR TEMPERATURE (1/10 DEGREES, LOW BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
A2 H
162 H
-
0
255
OUTSIDE AIR TEMPERATURE (1/10 DEGREES, HIGH BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
A2 L
162 L
-
0
255
OUTSIDE AIR TEMPERATURE (1/10 DEGREES, LOW BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
A3 H
163 H
-
0
255
RETURN AIR TEMPERATURE (1/10 DEGREES, HIGH BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
A3 L
163 L
-
0
255
RETURN AIR TEMPERATURE (1/10 DEGREES, LOW BYTE, 16 BIT
VALUE, 0 = -40 DEGREES F)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...