Sequence of Operation
When the outdoor temperature is equal to or less than
the
“LOW AMBIENT ECONOMIZER SETPOINT”
the
Simplicity Elite control will set the minimum position
of the outdoor damper to the programmed
“LOW
AMBIENT ECONOMIZER MINIMUM POSITION”
setting.
When the outdoor temperature is 1.0° F or more above
the
“LOW AMBIENT ECONOMIZER SETPOINT”
the
Simplicity Control will set the minimum position of the
outdoor damper to the programmed
“ECONOMIZER
MINIMUM POSITION”
setting.
EXHAUST FAN OPERATION
The Simplicity Elite control can be confi gured for the
following types of exhaust fan operation:
•
On/Off Control Based On Outdoor Damper Posi-
tion.
•
On/Off Control Based On Building Pressure.
•
Modulating Damper with Fixed Speed Ex-
haust.
•
Modulating Exhaust with a VFD.
On/Off Control Based on Outdoor Damper Posi-
tion
This exhaust option uses a standard motor without any
type of speed control and a barometric damper.
The following System Parameters must be programmed
through the Simplicity Elite control:
“POWER EXHAUST INSTALLED”
– must be turned
on using Parameter 43 under the PROGRAM key
on the Simplicity Elite control board or under the
ECONOMIZER/EXHAUST tab in the Simplicity PC
software package.
“ E C O N O M I Z E R D A M P E R P O S I T I O N F O R
EXHAUST FAN TO TURN ON”
– must be programmed
using Parameter 48 under the PROGRAM key
on the Simplicity Elite control board or under the
ECONOMIZER/EXHAUST tab in the Simplicity PC
software package.
“ECONOMIZER DAMPER POSITION FOR EXHAUST
FAN TO TURN OFF”
– must be programmed
using Parameter 49 under the PROGRAM key
on the Simplicity Elite control board or under the
ECONOMIZER/EXHAUST tab in the Simplicity PC
software package.
Sequence of Operation
When the output to the economizer damper is equal
to or greater then the
“ECONOMIZER DAMPER
POSITION FOR EXHAUST FAN TO TURN ON”
the
Simplicity Elite control closes the output to the exhaust
fan motor. The output is at the
“EXH”
terminal of the
P13 connector.
When the output to the economizer damper is equal to
or less then the
“ECONOMIZER DAMPER POSITION
FOR EXHAUST FAN TO TURN OFF”
the Simplicity
Elite control open the output to the exhaust fan motor.
The minimum run time is 10 seconds and the minimum
off time is 60 seconds.
On/Off Control Based on Building Pressure
This exhaust option uses a standard motor without any
type of speed control and a barometric damper.
The following System Parameters must be programmed
through the Simplicity Elite control:
“POWER EXHAUST INSTALLED”
– must be turned
on using Parameter 43 under the PROGRAM key
on the Simplicity Elite control board or under the
ECONOMIZER/EXHAUST tab in the Simplicity PC
software package.
“ B U I L D I N G S TAT I C P R E S S U R E S E N S O R
INSTALLED”
– must be turned on using Parameter 85
under the PROGRAM key on the Simplicity Elite control
board or under the EQUIPMENT INSTALLATION tab
in the Simplicity PC software package.
“BUILDING PRESSURE SETPOINT”
must be
programmed using Parameter 31 under the PROGRAM
key on the Simplicity Elite control board or under the
ECONOMIZER/EXHAUST tab in the Simplicity PC
software package.
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...