103
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
ADDRESS
NUMBER
DESCRIPTION
UNITS OF ADJUSTMENT
RANGE OF
ADJUSTMENT
CURRENT
SETTING
72/73/74/
75/76
ALARM ARRAY
DATA - 5 CHARACTERS
0 - 255
0
77
VAV / CV SELECTION
READ ONLY FLAG
CV = 0
VAV = 1
0
78
HOT GAS REHEAT
PARAMETER BIT
0 = OFF, 1 = ON
OFF
79
HOT GAS PRESENT ON COMPRESSOR # 1
PARAMETER BIT
0 = OFF, 1 = ON
OFF
80
COMPRESSORS AVAILABLE FOR COOLING
PARAMETER BIT
2 - 4
2
81
STAGES OF HEAT AVAILABLE
PARAMETER BIT
0 - 3
0 = DISABLED
2
82
DUCT STATIC READING
PRESSURE - INCHES OF
H2O
0.000 - 5.000
0000
83
BUILDING STATIC PRESSURE
PRESSURE - INCHES OF
H2O
0.000 - 5.000
0000
84
LOW AMBIENT KIT INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
85
BUILDING STATIC PRESSURE SENSOR INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
86
ERV INSTALLED
PARAMETER BIT
0 = OFF, 1 = ON
OFF
87
ERV UNOCCUPIED FAN ENABLE
PARAMETER BIT
0 = OFF, 1 = ON
OFF
88
DUCT STATIC SHUTDOWN SETPOINT
PRESSURE - INCHES OF
H2O
0.000 - 5.000
4.500
TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...