TABLE 2-14 – ELECTRIC HEAT
TABLE 2-15 – AIRFLOW AND ENTERING AIR/AMBIENT LIMITATIONS
* Cooling Only Units
KW
NOMINAL VOLTAGE
208/3/60
AMPS
230/3/60
AMPS
460/3/60
AMPS
575/3/60
AMPS
40
96
96
48
40
80
193
193
96
80
108
260
260
130
109
150
—
—
181
151
Limitations
Model Size
50
51
60
61
Minimum
Airflow at
Standard Design
Conditions.
CFM*
(min to max)
10000 -
22500
10000 -
22500
12500 -
24000
12500 -
24000
Entering Wet
Bulb Temp F°
(min/max)
57/75
57/75
57/75
57/75
Entering Dry
Bulb Temp F°
(min/max)
68/90
68/90
68/90
68/90
Ambient Temp F°
without Low
Amb option
50/120
50/120
50/120
50/120
Ambient Temp F°
with Low Amb
option
0/120
0/120
0/120
0/120
ELECTRIC DATA (CONTINUED)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...