![background image](http://html2.mh-extra.com/html/york/eco2-ypal-050/eco2-ypal-050_installation-and-operation-manual_4202925082.webp)
82
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Sequence of Operation
Sequence of Operation
Tables 5-4 thru 5-6 use the following defi nitions:
•
SAT COMFORT ZONE – the temperature be-
tween the
“COMFORT VENTILATION LOWER
SETPOINT”
minus 1.0° F and the
“COMFORT
VENTILATION UPPER SETPOINT”
plus 1.0°
F.
•
OAT COMFORT ZONE - the temperature be-
tween the
“COMFORT VENTILATION LOWER
SETPOINT”
and the
“COMFORT VENTILA-
TION UPPER SETPOINT”.
•
OAT
–
Outdoor
Air
Temperature.
•
SAT
–
Supply
Air
Temperature.
•
ECON OPERATION – Economizer damper will
open to BRING SAT into the SAT COMFORT
ZONE.
Conditions of Operation
•
In order for compressor operation
“COMFORT
VENTILATION FOR COOLING ENABLED”
must be enabled.
•
In order for heat stages to operate
“COMFORT
VENTILATION FOR HEATING ENABLED”
must be enabled.
•
Economizer operation will occur with either, or
both,
“COMFORT VENTILATION FOR COOL-
ING ENABLED”
or
“COMFORT VENTILA-
TION FOR HEATING ENABLED”
enabled.
EXCESSIVE SAT (SUPPLY AIR TEMPERATURE)
CONTROL
This feature is only available on Constant Volume
units. On a Constant Volume unit, the compressors
and heat stages are control by the space temperature
only, either by thermostat or zone sensor. As long as
the room device is calling for cooling or heating the
compressors or heating section does not control the
actual temperature of the supply air leaving the unit.
The enabling of this feature adds a means to prevent low
or high supply air temperatures from being delivered to
the conditioned space.
Cooling
T h e f o l l o w i n g S y s t e m P a r a m e t e r s m u s t b e
programmed:
“SUPPLY AIR TEMP LIMIT FOR COOLING
ENABLED”
- must be enabled using Parameter 14 under
the PROGRAM key on the Simplicity control board or
under the COOLING SETUP tab in the Simplicity PC
software package.
“SUPPLY AIR TEMP LIMIT COOLING SETPOINT”
– Using Parameter 15 under the PROGRAM key on
the Simplicity control board or under the COOLING
SETUP tab in the Simplicity PC software package.
If a single compressor is energized the control will
monitor the supply air temperature and respond as
follows:
TABLE 5-6 HEAT STAGE ON WHEN SPACE INPUT SATISFIED
OAT VS OAT COMFORT ZONE
SAT VS SAT COMFORT ZONE
ECON OPERATION
HEAT STAGE
COMP STAGE
BELOW
ABOVE
OPEN
LEAVE ON*
-
BELOW
BELOW
-
LEAVE ON
-
BELOW
WITHIN
-
LEAVE ON
-
ABOVE
ABOVE
-
TURN OFF
TURN ON
ABOVE
BELOW
OPEN
TURN OFF
-
ABOVE WITHIN
-
TURN
OFF
-
WITHIN
ABOVE
OPEN
TURN OFF
-
WITHIN
BELOW
OPEN
TURN OFF
-
WITHIN
WITHIN
-
TURN OFF
-
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...