138
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
Continued on next page
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
B4 H
180 H
70
50
85
MORNING WARM-UP AND VAV HEATING: RETURN AIR
TEMPERATURE SETPOINT (DEGREES F)
B5 H
181 H
60
0
200
DUCT PRESSURE SETPOINT (0.025” WC INCREMENTS, DEFAULT
= 1.500” WC « 60)
B5 L
181 L
180
0
200
DUCT PRESSURE SHUTDOWN SETPOINT (0.025” WC
INCREMENTS, DEFAULT = 4.500” WC « 180)
B6 H
182 H
70
0
100
BUILDING PRESSURE SETPOINT (0.005” WC INCREMENTS, 0 =
-0.250” WC, DEFAULT = 0.100” WC « 70)
B7 H
183 H
55
40
65
ECONOMIZER FIRST STAGE (UPPER) SETPOINT (DEGREES F)
B7 L
183 L
50
40
65
ECONOMIZER SECOND STAGE (LOWER) SETPOINT (DEGREES F)
B8 H
184 H
20
0
100
ECONOMIZER MINIMUM POSITION (PERCENT)
B9 H
185 H
27
10
50
ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT (BTU PER
POUND)
B9 L
185 L
27
10
50
ECONOMIZER RETURN AIR ENTHALPY SETPOINT (BTU PER
POUND)
BA H
186 H
55
40
80
ECONOMIZER OUTSIDE AIR TEMPERATURE ENABLE SETPOINT
(DEGREES F)
BB H
187 H
4
0
23
PRE-OCCUPANCY PURGE TIME (HOURS)
BB L
187 L
0
0
59
PRE-OCCUPANCY PURGE TIME (MINUTES)
BC H
188 H
80
10
100
EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN ON
– MODULATING ONLY (PERCENT)
BC L
188 L
20
0
90
EXHAUST DAMPER POSITION FOR EXHAUST FAN TO TURN OFF
– MODULATING ONLY (PERCENT)
BD H
189 H
60
10
100
ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN
ON – NON-MODULATING ONLY (PERCENT)
BD L
189 L
20
0
90
ECONOMIZER DAMPER POSITION FOR EXHAUST FAN TO TURN
OFF – NON-MODULATING ONLY (PERCENT)
BE H
190 H
0
0
80
SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR COOLING
(DEGREES F, 0 = DISABLED)
BE L
190 L
0
0
120
SUPPLY AIR TEMPERATURE ALARM SETPOINT FOR HEATING
(DEGREES F, 0 = DISABLED)
BF H
191 H
5
0
25
SPACE SENSOR ALARM TEMPERATURE (DEGREES F, 0 =
DISABLED)
BF L
191 L
60
0
120
SPACE SENSOR ALARM TIME (MINUTES, 0 = DISABLED)
C2 H
194 H
0
0
255
INTELLI-START RECOVERY TIME (MINUTES, 0 = DISABLED)
C3 H
195 H
-
-
-
ASCD TIMER FOR COMPRESSOR #1 HIGH BYTE
C3 L
195 L
-
-
-
ASCD TIMER FOR COMPRESSOR #1 LOW BYTE. (SECONDS,
COUNTS DOWN)
C4 H
196 H
-
-
-
ASCD TIMER FOR COMPRESSOR #2 HIGH BYTE
C4 L
196 L
-
-
-
ASCD TIMER FOR COMPRESSOR #2 LOW BYTE (SECONDS,
COUNTS DOWN)
C5 H
197 H
-
-
-
ASCD TIMER FOR COMPRESSOR #3 HIGH BYTE
C5 L
197 L
-
-
-
ASCD TIMER FOR COMPRESSOR #3 LOW BYTE. (SECONDS,
COUNTS DOWN)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...