140
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
User Interface Control Center
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
D7L
215 L
NA
0
-
-
OPTION BYTE #7
0
1 = ERV ENABLED
1
1 = ERV UNOCCUPIED FAN ENABLED
2-7
NA
D8 H
216 H
S
0
100
HOT GAS REHEAT HUMIDITY SETPOINT (PERCENT HUMIDITY)
D8 L
216 L
50
20
80
TEMPERATURE / HUMIDITY SETPOINT (PERCENT HUMIDITY)
D9 H
217 H
3
0
5
MAXIMUM TEMPERATURE / HUMIDITY OFFSET (DEGREES F)
D9 L
217 L
5
1
10
TEMPERATURE / HUMIDITY VALUE THAT = 1° F OF OFFSET
(PERCENT HUMIDITY)
DB H
219 H
72
45
99
OPERATING COOLING SETPOINT (DEGREES F) [CV]
DB L
219 L
68
45
99
OPERATING HEATING SETPOINT (DEGREES F) [CV]
DC H
220 H
-
10
50
OUTSIDE AIR ENTHALPY (BTUS PER POUND)
DC L
220 L
-
10
50
RETURN AIR ENTHALPY (BTUS PER POUND)
DE L
222 L
50
0
100
MAXIMUM DEMAND VENTILATION ECONOMIZER POSITION
(PERCENT OPEN)
DF H
223 H
-
0
10
SPACE SENSOR OFFSET (0 = -5° F, 10 = +5° F)
E0 H
224 H
-
-
-
ASCD TIMER FOR HEATING STAGE #1 (SECONDS, COUNTS
DOWN)
E0 L
224 L
-
-
-
HEATING STAGE #1 MINIMUM RUN TIMER (SECONDS, COUNTS
DOWN)
E1 H
225 H
-
-
-
ASCD TIMER FOR HEATING STAGE #2 (SECONDS, COUNTS
DOWN)
E1 L
225 L
-
-
-
HEATING STAGE #2 MINIMUM RUN TIMER (SECONDS, COUNTS
DOWN)
E2 H
226 H
-
-
-
ASCD TIMER FOR HEATING STAGE #3 (SECONDS, COUNTS
DOWN)
E2 L
226 L
-
-
-
HEATING STAGE #3 MINIMUM RUN TIMER (SECONDS, COUNTS
DOWN)
E3 H
227 H
0
0
99
LOW AMBIENT ECONOMIZER MINIMUM POSITION (PERCENT)
E3 L
227 L
0
0
60
LOW AMBIENT ECONOMIZER SETPOINT (DEGREES F)
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...