Furnace Status Input
The Unit Controller monitors the operation of the
Staged and Modulating Gas Heat sections and displays
the status through the STATUS screen of the User
Interface. The operation of each of the gas heat sections
is monitored by a multiplexer installed in the gas heat
section. When a gas heat section is energized, it sends a
24-volt signal to the multiplexer. The multiplexer takes
the fi ve “ON”/”OFF” inputs and converts them into a
0 to 5 volt DC signal that is sent to the Unit Controller.
The Unit Controller then decodes this analog input and
displays the furnace section status. Tables 8-9 and 8-10
show the relationship between the DC voltage and the
furnace operation status.
PPM CO2
OUTPUT
VOLTAGE
VDC
PPM CO2
OUTPUT
VOLTAGE
VDC
80
0.20
1120
2.80
160
0.40
1200
3.00
240
0.60
1280
3.20
320
0.80
1360
3.40
400
1.00
1440
3.60
480
1.20
1520
3.80
560
1.40
1600
4.00
640
1.60
1680
4.20
720
1.80
1760
4.40
800
2.00
1840
4.60
880
2.20
1920
4.80
960
2.40
2000
5.00
1040
2.60
TABLE 8-7 – CO2 SENSOR OUTPUT
CO
2
Sensor
Two CO
2
sensors are used in conjunction with the
“DEMAND VENTILATION”
option. In
“DEMAND
VENTILATION”
the Unit Control monitors the CO
2
level
of the outdoor air and the CO
2
level in the conditioned
space and varies the amount of ventilation air based on
the relationship between these two values. Table 8-7
gives the volts DC output for a given CO
2
level.
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...