TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
C6 H
198 H
-
-
-
ASCD TIMER FOR COMPRESSOR #4 HIGH BYTE
C6 L
198 L
-
-
-
ASCD TIMER FOR COMPRESSOR #4 LOW BYTE (SECONDS,
COUNTS DOWN)
C7 H
199 H
0
-
-
COMPRESSOR #1 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C7 L
199 L
0
-
-
COMPRESSOR #1 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
C8 H
200 H
0
-
-
COMPRESSOR #2 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C8 L
200 L
0
-
-
COMPRESSOR #2 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
C9 H
201 H
0
-
-
COMPRESSOR #3 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
C9 L
201 L
0
-
-
COMPRESSOR #3 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
CA H
202 H
0
-
-
COMPRESSOR #4 MINIMUM RUN TIMER HIGH BYTE (SECONDS,
COUNTS DOWN)
CA L
202 L
0
-
-
COMPRESSOR #4 MINIMUM RUN TIMER LOW BYTE (SECONDS,
COUNTS DOWN)
CB H
203 H
-
-
-
FAN ASCD TIMER HIGH BYTE (ALWAYS ZERO)
CB L
203 L
-
-
-
FAN ASCD TIMER LOW BYTE. (SECONDS, COUNTS DOWN)
CC H
204 H
0
-
-
FAN MINIMUM RUN TIMER (SECONDS, COUNTS DOWN)
CD H
205 H
0
-
-
FAN ON DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)
CD L
205 L
0
-
-
FAN OFF DELAY TIMER FOR HEAT (SECONDS, COUNT DOWN)
CE H
206 H
0
-
-
FAN ON DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)
CE L
206 L
0
-
-
FAN OFF DELAY TIMER FOR COOL (SECONDS, COUNT DOWN)
CF H
207 H
0
0
255
ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, HIGH
BYTE)
CF L
207 L
0
0
255
ACCUMULATED UNOCCUPIED OVERRIDE TIME (HOURS, LOW
BYTE)
D4 H
212 H
-
0
100
SUPPLY FAN VFD OUTPUT STATUS, 0-100% (2 – 10 VDC)
D4 L
212 L
-
0
100
EXHAUST DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)
D5 H
213 H
-
0
100
HOT WATER VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)
D5 L
213 L
-
0
100
HOT GAS REHEAT VALVE OUTPUT STATUS, 0-100% (2 – 10 VDC)
D6 H
214 H
-
0
100
ECONOMIZER DAMPER OUTPUT STATUS, 0-100% (2 – 10 VDC)
D7 H
215 H
NA
0
-
-
OPTION BYTE #6
0
1 = COMFORT VENTILATION FOR COOLING ENABLED
1
1 = COMFORT VENTILATION FOR HEATING ENABLED
2
1 = TEMPERATURE / HUMIDITY CONTROL ENABLED
3
1 = HOT GAS REHEAT ALTERNATE OPERATION ENABLED
4
1 = NETWORK OCCUPIED FLAG: OCC IS ON
5
NA
6
1 = DIFFERENTIAL ENTHALPY MODE ENABLED
7
NA
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...