133
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
6
Continued on next page
TABLE - 6-2 - SIMPLICITY ELITE DATA MAP (CONT.)
ADDRESS
(HEX)
ADDRESS
(DEC)
BIT
INITIAL/
DEFAULT
VALUE
(HEX)
MIN
VALUE
MAX
VALUE
DESCRIPTION
0
BITS 1 AND 0 = 0,0 RESPECTIVELY THERE ARE 2 STAGES OF
COMPRESSION; 0,1 = 3 STAGES; 1,0 = 4 STAGES; 1,1 = 4
STAGES
1
2
1 = SAT LIMIT FOR COOLING ENABLED
3
1 = SAT LIMIT FOR HEATING ENABLED
4
1 = HYDRONIC HEATING ENABLED
5
1 = HYDRONIC HEAT ACTUATOR VALVE REVERSE ACTING
6
1 = REMOTE CONTROL INPUT ENABLED FOR THIRD PARTY BAS
7
1 = HOT GAS REHEAT ENABLED
1A L
26 L
NA
4
-
-
OPTION BYTE #3
0
1 = VAV OCCUPIED HEATING ENABLED
1
NA
2
1 = ECONOMIZER PRESENT
3
1 = OUTSIDE AIR HUMIDITY SENSOR PRESENT
4
1 = RETURN AIR HUMIDITY SENSOR PRESENT
5
1 = PRE-OCCUPANCY PURGE ENABLED
6
1 = DEMAND VENTILATION ENABLED
7
1 = BUILDING PRESSURE SENSOR INSTALLED
1B H
27 H
NA
193
-
-
OPTION BYTE #4
0
1 = POWER EXHAUST PRESENT
1
1 = MODULATING POWER EXHAUST PRESENT
2
1 = EXHAUST VFD PRESENT
3
1 = LOW AMBIENT KIT INSTALLED
4
1 = DIRTY FILTER SWITCH PRESENT
5
1 = INTELLI-START OPERATION ENABLED
6
1 = INDOOR FAN OPERATES WITH SPACE SENSOR PRESENT [CV]
7
1 = DAYLIGHT SAVINGS TIME ENABLED
1B L
27 L
NA
8
-
-
OPTION BYTE #5
0
1 = RUN TEST ENABLED
1
1 = METER OF UNOCCUPIED OVERRIDE ENABLED
2
1 = METRIC DISPLAY ENABLED
3
1 = USE THERMOSTAT OR COMMUNICATIONS FLAG FOR
OCCUPIED SIGNAL
4
1 = LEAD/LAG: EQUALIZE COMPRESSOR RUN TIME ENABLED
5
1 = HOT GAS BYPASS PRESENT ON COMPRESSOR #1
6
1 = THIRD PARTY BAS ECONOMIZER ENABLED
7
1 = MORNING WARM-UP ENABLED
1C H
28 H
NA
0
0
255
ALARM 1 - MOST RECENT ALARM.
1C L
28 L
NA
0
0
255
ALARM 2
1D H
29 H
NA
0
0
255
ALARM 3
1D L
29 L
NA
0
0
255
ALARM 4
1E H
30 H
NA
0
0
255
ALARM 5 – OLDEST STORED ALARM.
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...