5
Occupied Heating
There are three stages of heating available:
•
W1 – First Stage of Heating
•
W2 – Second Stage of Heating
•
W3 – Third Stage of Heating
See the Heating section of this manual for a description
of the heating staging.
Unoccupied Heating
Unoccupied heating operation is the same as Occupied.
A programmable thermostat would be required in order
to change the heating temperature settings between
occupied and unoccupied.
Space Sensor – Hard Wired or Communicated
The following System Parameters must be programmed
through the Simplicity Control:
•
“CV OCCUPIED COOLING SETPOINT”
– us-
ing Parameter 10 under the PROGRAM key on
the Simplicity control board or under the COOL-
ING SETUP tab in the Simplicity PC software
package.
•
“CV OCCUPIED HEATING SETPOINT”
– us-
ing Parameter 11 under the PROGRAM key on
the Simplicity control board or under the HEAT-
ING SETUP tab in the Simplicity PC software
package.
•
“CV UNOCCUPIED COOLING SETPOINT”
– using Parameter 12 under the PROGRAM
key on the Simplicity control board or under
the COOLING SETUP tab in the Simplicity PC
software package.
•
“CV UNOCCUPIED HEATING SETPOINT”
– using Parameter 13 under the PROGRAM
key on the Simplicity control board or under
the HEATING SETUP tab in the Simplicity PC
software package.
Cooling Operation – Occupied or Unoccupied
The Simplicity Control will stage on the cooling as
follows:
•
At cooling start up
– If the space temperature is between 1.5° F and
1.9° F above the
“CV OCCUPIED COOLING
SETPOINT”
or
“CV UNOCCUPIED COOL-
ING SETPOINT”
the control will turn on the
fi rst compressor from System 1 and turn on a
5 minute timer.
– If after 5 minutes the space temperature is
between 1.5° F and 1.9° F above the
“CV
OCCUPIED COOLING SETPOINT”
or
“CV
UNOCCUPIED COOLING SETPOINT”
the
control will bring on the second compressor
of System 1 and start a 5-minute timer.
OR
– If the space temperature is greater than 2.0° F
or more above the
“CV OCCUPIED COOL-
ING SETPOINT”
or
“CV UNOCCUPIED
COOLING SETPOINT”
the control will bring
on the fi rst compressor from System 1 and
start a 3 minute timer. After 30 seconds, the
control will bring on the second compressor
from System 1.
•
If after 3 or 5 minutes the space temperature is
between 1.5° F and 1.9° F above the
“CV OC-
CUPIED COOLING SETPOINT”
or
“CV UN-
OCCUPIED COOLING SETPOINT”
the control
will bring on the fi rst compressor from System 2
and start a 5 minute timer.
•
If after 3 or 5 minutes the space temperature
is 2.0° F or more above the
“CV OCCUPIED
COOLING SETPOINT”
or
“CV UNOCCUPIED
COOLING SETPOINT”
the control will bring
on the fi rst compressor of System 2 and start a 3
minute timer.
•
If after 3 or 5 minutes the space temperature
is 1.5° F or more above the
“CV OCCUPIED
COOLING SETPOINT”
or
“CV UNOCCUPIED
COOLING SETPOINT”
the control will bring on
the second compressor of System 2.
Summary of Contents for ECO2 YPAL 050
Page 62: ...62 JOHNSON CONTROLS FORM 100 50 NOM6 1207 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 113: ...113 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ECONOMIZER EXHAUST LD13018...
Page 114: ...114 JOHNSON CONTROLS FORM 100 50 NOM6 1207 User Interface Control Center FANS LD13019...
Page 115: ...115 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 COOLING SETUP LD13020...
Page 117: ...117 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 HEATING SETUP LD13022...
Page 119: ...119 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 SYSTEM OPTIONS LD13024...
Page 121: ...121 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 INPUTS COMFORT DEMAND VENTILATION LD13014 LD13026...
Page 125: ...125 JOHNSON CONTROLS FORM 100 50 NOM6 1207 6 ALARMS LD13031...